AFCI Troubleshooting
Card
For both 1- and 2-pole breakers, LED
indications will appear for 5 seconds each time
the AFCI is turned "ON" and will display each
time the beaker is reset for up to 30 days after
the last trip. The last known trip condition can
cleared by the following process:
1. Turn the AFCI to the "OFF" position.
2. Press and hold Push-to-Test (PTT) button(s).
3. Turn the AFCI to the "ON" position.
4. Release PTT button(s) within 3 seconds.
---
LED
Test button
LED 1
LED 2
Test
buttons

Other manuals for Siemens AFCI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens AFCI and is the answer not in the manual?

Siemens AFCI Specifications

General IconGeneral
Interrupting Rating10kA
TypeAFCI (Arc Fault Circuit Interrupter)
Amperage Rating15A, 20A
Poles1
StandardsUL 1699
MountingPlug-in