WL Circuit Breaker
1/37
WL Selection and Application Guide • 2005
Technical Data
WL Circuit Breaker
Function Overview of the Electronic Trip Units
Basic Functions ETU725 ETU727 ETU745
Parameter sets
Selectable between
parameter set A and B
LCD
LCD, alphanumeric (4-line)
O
LCD, graphic
Communication
CubicleBUS integrated
Communication capability via
MODBUS or PROFIBUS
Metering function
Metering function capability with
Metering Function or
Metering Function PLUS
Display by LED
Trip unit active ✔✔
Alarm ✔✔
ETU error ✔✔
L trip ✔✔
S trip ✔✔
I trip ✔✔
N trip ✔✔
G trip ✔✔
(only with ground fault module)
G alarm (only with ground fault module)
Tripped by extended protection or
protective relay function
Communication
Signal contacts with external CubicleBUS modules
(Opto or relay)
Overcurrent warning
Load shedding OFF/ON
Early signal of long time trip (200 ms)
Temperature alarm
Phase unbalance
Instantaneous trip
Short-time trip
Long-time trip
Neutral conductor trip
Ground fault protection trip
(only with ground fault module)
Ground fault alarm (only with ground fault module)
Auxiliary relay
ETU error
available
not available
O optional
from … to step from … to step
0… 1 0.1 1000… 1600 50
1… 100 1 1600… 10000 100
100… 500 5 10000… max 1000
500… 1000 10
Step for Settings via Communications or ETU Key Pad
Setting range of the I
g
Frame Size II Frame Size III
A 100A 400A
B 300A 600A
C 600A 800A
D 900A 1000A
E 1200A 1200A