EasyManua.ls Logo

Siemens WL - Page 60

Siemens WL
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data for Current Transformers
WL Circuit Breaker
1/56
WL Selection and Application Guide • 2005
Neutral Sensors for Modified Differential Ground Fault
Frame Size I & II
Neutral Sensors for Modified Differential Ground Fault
Frame Size III
Catalog Number Current Ratio Accuracy
WLGMDGFCT2 3200:2.67 0.3% at 45VA 3.10
resistive burden
Frequency: 50 - 400 Hz
Insulation Level:
0.6 kV; BIL 10 kV full wave
Insulation System:
Cast in polystyrene resin, red or black,
Temperature Class 130º C
Continuous Thermal Current Rating Factor:
1.33 @ 30º C ambient; 1.00 @ 55º C ambient
Regulatory Agency Approval:
UL and CUL
Flexible Leads:
UL-1015, CSA approved, #16 AWG, 36" long
(minimum), with wire markers
Approximate Weight: 20 lbs.
Tolerance on Dimension
(unless otherwise noted):
0.06 for dimension under 6"
0.09 for dimension between 6" & 18"
Catalog Number Current Ratio Accuracy
WLGMDGFCT3 5000:4.17 0.3% at 45VA 1.94 224
resistive burden
Frequency: 50 - 400 Hz
Insulation Level:
0.6 kV; BIL 10 kV full wave
Insulation System:
Cast in polyurethane resin, red or black,
Temperature Class 130º C
Continuous Thermal Current Rating Factor:
1.33 @ 30º C ambient; 1.00 @ 55º C ambient
Regulatory Agency Approval:
UL and CUL
Flexible Leads:
UL 1015, CSA approved, #16 AWG, 36" long
(minimum), with wire markers
Approximate Weight: 33 lbs.
Tolerance on Dimension
(unless otherwise noted):
0.06 for dimension under 6"
0.09 for dimension between 6" & 18"
0.125 for dimension over 18"
Secondary Winding
Resistance
(ohms @ 75
º
C
Thermal
S/T
kA - 1 sec
Secondary Winding
Resistance
(ohms @ 75
º
C
Thermal
S/T
kA - 1 sec
+
-
+
-
+
-
+
-
+
-
WL_SA_intro-sec1.qxd 2/7/05 1:56 PM Page 58