(If Li is selected in program 5, this program can’t be set up)
The MPPT charger will stop when charging is completed. To activate the charger, the battery voltage must
drop at least 2 voltages below the lower value in program 19 and 20.
Program 03: AC Input Voltage Range
03 APL: Appliance Mode
In Appliance Mode, the acceptable AC input voltage range is
MS6048D
90~280VAC±7V.
03:UPS
In UPS Mode, the acceptable AC input voltage range:
MS6048D
170~280VAC±7V.
03: GEN
In Generator Mode, the acceptable AC input voltage range:
MS6048D
90~280VAC±7V
Note: When the inverter is connected to a generator, the generator should be more than twice the inverter
nominal power.
Program 04: Power Saving Mode Enable/Disable
04: SdS
When the power saver mode is disabled, the inverter will output full voltage, and the idle power is about
50-60 watts.
04: SEN
If the power saver mode is enabled, the output of inverter will be off when connected load is low or not
detected.
The threshold for load detection is 100W. The idle power in power saver mode is about 30 watts.
Program 05: Battery Type
05: AGN
AGM Battery (Default) : CV :56.4V, Float 54V.
05: FLd
Flood Battery: CV :58.4V, Float 56V.
05: USE
User-Defined
If “User-Defined” is selected, battery charge voltage and low DC cut-off voltage can be set up in program
19, 20 and 21. This setting works for GEL batteries etc.