- 1 -
TPH Series Transformer based
3 Phase Pure Sine Wave Inverter Charger
24V/48V to 120/208Vac & 230/400Vac
6KW to 45KW
User’s Manual
Version 1.0
Sigineer Power Limited
Email: info@sigineer.com
TEL: +86 0769 82817616
Manufacturer Information

Questions and Answers

  • S
    Steven LopezAug 13, 2025
    Why does my Sigineer Power Inverter charger turn off when charging from a generator?
    • J
      Jorge CarterAug 13, 2025
      If your Sigineer Power Inverter charger turns off while charging from a generator, it might be due to high AC input voltages from the generator. To resolve this, try loading the generator down with a heavy load or turning down the generator's output voltage.
  • L
    lisa00Aug 17, 2025
    Why is my Sigineer Power Inverter charger supplying a lower charge rate?
    • E
      erin88Aug 17, 2025
      If your Sigineer Power Inverter is supplying a lower charge rate, it could be due to several reasons: * Improperly set charger controls. * Low AC input voltage. * Loose battery or AC input connections. Refer to the section on adjusting the "Charger Rate", ensure a qualified AC power source is used, and check all DC/AC connections.
  • B
    Brian HollowayAug 20, 2025
    Why is there noise coming from the transformer/case of my Sigineer Power TPH Inverter?
    • J
      Jeffery BishopAug 21, 2025
      If you're experiencing noise from the transformer or case of your Sigineer Power Inverter, it's likely due to applying specific loads such as a hair dryer. Try removing these loads to see if the noise stops.
  • M
    Michael TurnerAug 25, 2025
    What to do if the Sigineer Power Inverter charger is inoperative and won't accept AC?
    • D
      Daniel BakerAug 25, 2025
      If your Sigineer Power Inverter charger is inoperative and won't accept AC, it's possible that the AC voltage has dropped out of tolerance. Check the AC voltage to ensure it's within the proper voltage and frequency range.
  • D
    Danielle RyanAug 28, 2025
    What to do if the AC output voltage is low on my Sigineer Power TPH Inverter?
    • S
      Stephanie GarrisonAug 28, 2025
      If the AC output voltage from your Sigineer Power Inverter is low and it turns loads off quickly, it's likely due to a low battery. Check the condition of your batteries and recharge them if possible.
  • A
    Andrea WoodsAug 31, 2025
    Why do sensitive loads turn off when using my Sigineer Power TPH?
    • M
      Martha GrantAug 31, 2025
      If your sensitive loads are turning off when using your Sigineer Power Inverter, the inverter's low voltage trip voltage may be too low to sustain certain loads. Try choosing a narrow AC voltage range in the DIP switch settings. If the problem persists, consider installing a UPS.
  • D
    Donald WeaverSep 4, 2025
    How to troubleshoot a Sigineer Power TPH that will not turn on?
    • T
      Taylor LewisSep 4, 2025
      If your Sigineer Power Inverter won't turn on during initial power up, it could be due to several reasons: * Batteries are not connected or have loose connections. * Low battery voltage. Check the batteries and cable connections, inspect the DC fuse and breaker, and ensure the battery is charged.
  • O
    Olivia SmithSep 8, 2025
    What to do if my Sigineer Power TPH Inverter has no AC output and no lights are on?
    • J
      James PerrySep 8, 2025
      If there is no AC output voltage and no indicator lights are on for your Sigineer Power Inverter, the inverter may have been manually transitioned to OFF mode. Press the switch to either the Power saver on or Power saver off position.

Sigineer Power TPH Series Specifications

General IconGeneral
BrandSigineer Power
ModelTPH Series
CategoryInverter
LanguageEnglish