Allow utility to charge the battery all day run.
0000(default)
The timer allows utility to charge the battery at preset time.
Use 4 digits to represent the time period, the upper two digits represent the time when utility start to charge
the battery, setting range from 00 to 23, and the lower two digits represent the time when utility end to
charge the battery, setting range from 00 to 23.
(eg: 2320 represents the time allows utility to charge the battery is from 23:00 to the next day 20:59, and the
utility charging is prohibited outside of this period)
Program 50 AC output time
Allow inverter to power the load all day run.
0000(default)
The timer allows inverter to power the load at preset time.
Use 4 digits to represent the time period, the upper two digits represent the time when inverter start to power
the load, setting range from 00 to 23, and the lower two digits represent the time when inverter end to power
the load, setting range from 00 to 23.
(eg: 2320 represents the time allows inverter to power the load is from 23:00 to the next day 20:59, and the
inverter AC output power is prohibited outside of this period)
Note:
Some of the program settings are interlocked with other settings, for example:
1 When the program 05 is set to AGM、FLD、LI, the program 19, 20 and 21 will be locked to factory default
value.
2 When program 05 is set to LI, the program 02 max charging current setting will be locked.