CCP 521 C-DIAS PROCESSOR MODULE
Page 26 15.03.2016
An error has occurred while ac-
cessing a DIAS module.
Possible Causes:
- An attempt is made to access a
nonexistent DIAS module.
- DIAS bus error.
Solution:
- Check the DIAS bus
- Check the termination resistors.
The operating system is currently
being reprogrammed.
The operating system has been
reinstalled.
The operating system cannot be
loaded; too little memory.
Boot loader message.
No operating system found in
RAM.
The boot loader is searching for
the operating system in RAM.
The operating system loaded does
not match the hardware configura-
tion.
The LASAL Module or project
cannot be loaded.
A general error has occurred while
loading the operating system.
An error has occurred in the
application memory (user heap).