In the VARAN Manager, an error
number was stored and the pro-
gram execution was stopped.
Possible causes:
- Real network does not match
the project
Solution:
- Read log file
A required VARAN Client was
removed or a communication error
has occurred. The program execu-
tion has stopped.
Possible causes:
- Damaged wiring
- Missing energy supply for
decentralized modules
Solution:
- Read Log file
- Analyze error tree
An error has occurred while
loading the application.
An error has occurred while
attempting to save the application.
Read or write access of a restrict-
ed memory area. (I.e. writing to the
NULL pointer).
An exception error caused by
exceeding the memory limits
An unauthorized instruction for the
current CPU level was given. For
example, setting the segment
register.
An error has occurred during a
floating-point operation.
Error from the Intelligent DIAS-
Master.
An internal error has occurred, all
applications are stopped.
Restart; report error to Sig-
matek.
An error has occurred during a file
operation.
Restart; report error to Sig-
matek.
The total duration of all real-time
objects exceeds the maximum
time; the time cannot be config-
ured.
2 ms for 386 CPUs
1 ms for all other CPUs
Starting from Version 1.1.7