IntelliKnight 5820XL Basic Operating Instructions
These instructions must be framed and displayed next to the IntelliKnight 5820XL
panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems.
Operation Keystrokes
Silence alarms and
troubles
Press then rotate the key or enter a code
Reset alarms
Press then rotate the key or enter a code.
Conduct a fire drill
1. Rotate the key or enter a code to access the menu, then press .
2. Press to select Fire Drill.
3. Press any key to begin the drill. To end the drill, press any key.
To conduct a fire drill from a remote fire drill switch:
Activate the switch to begin the drill; de-activate the switch to end the drill.
View alarms and troubles
When the system is in alarm or trouble, press to view location and type of alarm or
trouble.
View status of point
1. Rotate the key or enter a code to access the menu, then press .
2. Press for Point Status.
3. From the list that displays, select the 5815XL module where the point you want to
view is located. The screen that displays tells the status of the point including whether
detector sensitivity is in compliance (see below).
Check detector sensitivity
1. Rotate the key or enter a code to access the menu, then press .
2. Press for Point Status.
3. From the list that displays, select the 5815XL module where the point you want to
view is located.
4. The fourth line of the display shows the sensitivity status.
“NORMAL” means the detector is in compliance with NFPA 72.
“CAL MAINT” means the detector is in compliance with NFPA 72 but
maintenance should be performed soon.
CAL TRBLE” means the detector is not in compliance with NFPA 72.
Set Time and Date
1. Rotate the key or enter a code to access the menu, then press .
2. Make changes in the fields on the screen as necessary.
3. When the time and date are correct, press .
Enable / Disable point
1. Rotate the key or enter a code to access the menu.
2. Press for Point Functions.
3. Press for Disable / Enable point.
4. From the list that displays, press to select the 5815XL module where the
point you want to disable or enable is located.
5. Press to toggle the point between NORMAL (enabled) and DISABLE.
View event history
Rotate the key or enter a code to access the menu, then press to select Event
History. Events will display in date order, with most recent events displaying first.
Form #: 151141 Rev. A, 11/98
SILENCE
RESET
1
1
2
2
2
2
4
ENTER
2
1
ENTER
3

Other manuals for SILENT KNIGHT INTELLIKNIGHT 5820XL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SILENT KNIGHT INTELLIKNIGHT 5820XL and is the answer not in the manual?

SILENT KNIGHT INTELLIKNIGHT 5820XL Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC, 18 AH
Event History Log1000 events
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
Display80-character LCD
Communication PortsRS-232, RS-485
ProgrammingVia PC software
Zones99 software zones
NAC Circuits4 built-in, expandable
CommunicationBuilt-in digital communicator
Max Initiating Device Circuits (IDCs)Not applicable
Communication OptionsIP, Cellular
CertificationsUL, FM, CSFM

Related product manuals