16 Technical Data
SMA Solar Technology AG
Operating manual STP110-60-BE-en-16 103
16 Technical Data
16.1 General Data
Width x height x depth 1117mm x 682mm x 363mm
Weight with enclosure lid and connecting plate 93.5 kg
Length x width x height of the packaging 1220mm x 840mm x 618mm
Transport weight 125 kg
Climatic category in accordance with IEC
60721‑3‑4
4K4H
Environmental category Outdoors
Pollution degree of all enclosure parts 2
Operating temperature range -30°C to +60°C
Maximum permissible value for relative humid-
ity, condensing
100%
Maximum operating altitude above mean sea
level (MSL)
3000 m
Typical noise emission 78dB(A)
Power loss in night mode < 5W
Power control / Demand response (DRED) Communication via Modbus interface
Export limiting in accordance with AS/
NZS4777.2
EDMM-10, EMETER-20
Demand response mode in accordance with
AS/NZS4777.2
DRM0
Topology Transformerless (Non-isolated)
Cooling method Active cooling
Number of fans 5
Degree of protection for electronics in accor-
dance with IEC60529
IP66
Protection class in accordance with
IEC62109-1
I
16.2 DC Input
Maximum PV array power 165000 Wp STC
Maximum input voltage 1100V
MPP voltage range 200V to 1000V