What causes installation fault (Event 1101) on SMA Inverter?
- VVictor SullivanSep 4, 2025
If your SMA Inverter displays 'Installation fault' (Event 1101), a second phase is connected to N. Correct the connection.
What causes installation fault (Event 1101) on SMA Inverter?
If your SMA Inverter displays 'Installation fault' (Event 1101), a second phase is connected to N. Correct the connection.
How to check ground fault on SMA SUNNY BOY 3600TL?
To check for ground faults on your SMA Inverter, indicated by event number '35', '36' or '37': 1. Open the Sunny Boy. 2. Measure the voltages between the plus and minus pole of a string against the ground potential. If a voltage is present, there is a ground fault in the corresponding string. 3. Repeat step 2 for each string.
What to do if my SMA SUNNY BOY 3600TL is waiting for grid voltage?
If the SMA Inverter shows a 'Waiting for grid voltage' error, it means there's no mains voltage at the AC output. First, check the fuse and replace it if necessary. Then, inspect the AC installation and check for a general power failure.
What does it mean if my SMA Inverter displays 'Unstable operation (Event 3301 ... 3303)'?
If your SMA Inverter displays 'Unstable operation (Event 3301 ... 3303),' it means there is not enough power at the DC input of the inverter for stable operation. Wait until irradiation is higher. If this event recurs at medium irradiation levels, check the PV plant design and the correct circuitry of the PV array.
What does it mean if my SMA SUNNY BOY 3600TL Inverter reports varistor defective (Event 7401)?
If your SMA Inverter indicates that the varistor is defective (Event 7401), at least 1 of the thermally monitored varistors is defective. Check varistors.
What to do if SMA SUNNY BOY 3600TL Inverter shows system disturbance (Event 202 ... 205)?
If your SMA Inverter displays a system disturbance related to Event 202-205, this means that the mains voltage has fallen below the permissible range. Check whether the miniature circuit-breaker has tripped. Check the mains voltage and grid connection on the inverter. If the mains voltage is outside the permissible range due to local grid conditions, ask your network operator if the voltage can be adjusted at the feed-in point or if it would be acceptable to change the monitored operating limits. If the mains voltage is within the tolerance range, yet this error is still displayed, contact the SMA Service Line.
Why is my SMA SUNNY BOY 3600TL Inverter waiting for DC start conditions (Event 3901 to 3902)?
If your SMA Inverter displays 'Waiting for DC start conditions' (Event 3901 to 3902), the input power or voltage of the PV modules is not yet sufficient for feeding into the electricity grid. Wait until irradiation is higher. If this event recurs at medium irradiation levels, check the PV plant design and the correct circuitry of the PV array.
How to fix external fan fault (Event 7508) on SMA Inverter?
If your SMA Inverter shows an external fan fault (Event 7508), the fan is either clogged or defective. Clean the fan or replace it.
What to do if my SMA SUNNY BOY 3600TL displays 'Waiting for DC start conditions (Event 3901 ... 3902)'?
If your SMA Inverter displays 'Waiting for DC start conditions (Event 3901 ... 3902),' the input power or voltage of the PV modules is not yet sufficient for feeding into the electricity grid. Wait until irradiation is higher. If this event recurs at medium irradiation levels, check the PV plant design and the correct circuitry of the PV array.
What does DC overvoltage (Event 3401 to 3402) mean on my SMA Inverter?
If your SMA Inverter displays a 'DC overvoltage' error (Event 3401 to 3402), it means the DC input voltage connected to the inverter is too high. Disconnect the inverter from the PV array immediately. Check that the DC voltage of the strings is in compliance with the input voltage range of the inverter before reconnecting the inverter to the PV array. If the voltage is within the permissible input voltage range, the inverter may be defective. Contact the SMA Service Line.
Rated Output Power | 3600 W |
---|---|
Max. input voltage | 600 V |
Number of MPP Trackers | 1 |
Max. apparent AC power | 3600 VA |
Nominal AC voltage | 230 V |
Protection Class | IP65 |
Operating Temperature Range | -25 °C to +60 °C |
AC Voltage Range | 184 V - 276 V |
Frequency Range | 50 Hz / 60 Hz |
Cooling | Convection |