11 Troubleshooting
SMA Solar Technology AG
Operating manualSTP8-10-3AV-40-BE-en-1278
Event number Message, cause and corrective measures
3801
3802
3805
DC overcurrent > Check generator
Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.
Corrective measures:
If this message is displayed frequently, ensure that the PV array has been
correctly rated and wired.
3901
3902
Waiting for DC start conditions > Start conditions not met
The feed-in conditions for the utility grid are not yet fulfilled.
Corrective measures:
Ensure that the PV array is not covered by snow or otherwise shaded.
Wait for higher irradiation.
If this message is displayed frequently in the morning, increase the
voltage limit for starting grid feed-in. Change the parameter Critical
voltage to start feed-in.
If this message is displayed frequently with medium irradiation, ensure
that the PV array is correctly rated.
4011
Bridged strings detected
The DC inputs A and B are connected in parallel.
4012
No bridged strings detected
The DC inputs A and B are not connected in parallel.
6002-6412
Self-diagnosis > Interference device
The cause must be determined by the Service.
Corrective measures:
Contact the service.