13 Technical Data
SMA Solar Technology AG
Operating manual STP8-10-3AV-40-BE-en-12 97
13 Technical Data
13.1 DC/AC
13.1.1 SunnyTripower 8.0 / 10.0
STP8.0-3AV-40 STP10.0-3AV-40
Maximum PV array power 15000Wp 15000Wp
Maximum input voltage 1000V 1000V
MPP voltage range 260V to 800V 320V to 800V
Rated input voltage 580V 580V
Minimum input voltage 125V 125V
Initial input voltage 150V 150V
Maximum input current, input A 20A 20A
Maximum input current, input B 12A 12A
Maximum short-circuit current,
inputA*
30 A 30 A
Maximum short-circuit current,
input B*
18 A 18 A
Maximum reverse current into
the PV array
0A 0A
Number of independent MPP
inputs
2 2
Strings, input A 2 2
Strings, input B 1 1
Surge category in accordance
with IEC60664-1
II II
* In accordance with IEC62109-2: ISC PV
AC Output
STP8.0-3AV-40 STP10.0-3AV-40
Rated power at 230V, 50Hz 8000W 10000W
Maximum apparent AC power
at cosφ=1
8000VA 10000VA
Rated grid voltage 230V 230V