3. Select SCALE ZEROING.
4. Make sure that the tank is empty and press OKAY.
5. Wait.
6. Display will read COMPLETED.
Vacuum Calibration
Vacuum calibration must not be performed unless it is absolutely necessary. If there is a
problem with vacuum calibration, please call technical service.
1. Hoses must be unattached, with adapters connected.
2. Hoses should be free of refrigerant.
3. Detach new oil bottle.
4. Press SERVICE then CALIBRATIONS.
5. Select VACUUM CALIBRATION.
6. Vacuum pump will start running.
7. Wait for the counter to reach zero.