If the stop is input from the EMG or RESET terminal or the stop-switch on the connected
Teaching Box during pushing operation, the electric actuator stop. ("Busy" signal turns OFF)
If the electric actuator stops within the range of "Position" ± "In posn" as defined in the step
data, the output signal "INP" will turn ON.
When the servomotor is OFF, SVRE is OFF. When the servomotor is ON, SVRE is ON.
During activation of Teaching Box stop switch, this terminal is OFF. During the normal operation,
this is ON. This is synchronized to the input terminal for the EMG signal.
When there are no alarms, this terminal is ON.
When there are alarms, this is OFF.
*1) The "*ALARM" and "*ESTOP" are the negative-true logic output
The table below shows the changes in the output signal with respect to controllers state.
Servo is OFF when the controller is powered
for the first time
Note 1)
Servo is ON when the controller is powered for
the first time
Controller powered down [SVOFF] with no motion
Controller powered down [SVON] with no motion
During returning to origin, [SETUP].
The electric actuator is at the origin. On completion of
[SETUP]
During movement by positioning/ pushing operation.
The electric actuator is paused by [HOLD]
On completion of the positioning operation.
(within "In position")
Stopped due to pushing a work-load in pushing
operation. (holding)
Stopped due to no detection of work-load during a
pushing operation.
On completion of return to origin and then with
[SVON] turned off.
EMG signal stop from the CN1 connector after the
electric actuator is at the origin.
*1) Alarm “Absolute encoder ID Alarm error” is canceled.
*2) The output turns on when the electric actuator is "In position" of the step data.
*3) Return to origin completed.
*4) Retains the previous state.
*5) The output turns on when the electric actuator is within the range defined in the basic parameter setup.
*6) The output is updated on the transition of (ON→OFF) of the DRIVE input signal.