The Socket & See MFT5000 Loop test function has 2 modes for Loop testing that allow
the user to conduct the most accurate test possible whether or not the circuit under test
is protected by an RCD.
Intermittent Operation
The Socket & See MFT5000 is designed for a large number of loop tests in rapid
succession. In the unlikely condition this limit is exceeded a thermometer will be shown
on the display until the unit cools down. Testing will be inhibited while the thermometer
is shown.
Mains Supply Wiring and Voltage Test
When first connected to a mains supply the Socket & See MFT5000 will automatically
conduct a safety test to ensure that the Live, Neutral and Earth conductors are all
connected correctly and that the supply voltage is in the acceptable range (207-230V)
If all is well the VOLTAGE/POLARITY warning LED will light Green and the supply
voltage will be displayed in the primary display area.
In the event of a problem with either the mains voltage supply or reversed connections
the VOLTAGE/POLARITY warning LED will light Red, a warning tone will be sounded
and testing will be inhibited.
This condition will be indicated for you safety.
18