EasyManua.ls Logo

Socket & See MFT5000 - General Specifications

Socket & See MFT5000
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Dimensions
H 115mm W 245mm D 140mm
Weight (With Baeries)
965g
Baery Type
6 x AA / LR6 Alkaline
Baery Life (Typical)
Idling : 13.5 hours
1
Insulaon according to BS EN61557-2: 1008 tests
Connuity according to BS EN61557-4: 960 tests
Protecve Device
F0.5A, 500V, HRC 6.3 x 32mm
LCD Display
TFT (Thin-Film-Transistor) Colour LCD 3.5” Diagonal
320xRGBx240 pixels
Category Rang
300V CAT IV
600V CAT III
Ingress Protecon Rang
IP54
Operang Temperature
0°C to 40°C
Storage Temperature
-10°C to 60°C
Operang Humidity
80% @ 31°C to 50% @ 40 °C
Operang Altude 0 to 2000m
General Specifications
0.00 to 500.0
± (5% + 5
digits)
195 - 253 V ac 50-60 Hz 550 V
Measurement
Range
Accuracy
System
Voltage Range
System Voltage
Frequency
Over Voltage
Protection
(BS EN 61557-10)
Measurement
Range
Accuracy
System
Voltage Range
System Voltage
Frequency
Over Voltage
Protection
(BS EN 61557
0.00 to 500.0
± (3% + 3
digits)
100 - 440 V ac 50-60 Hz 550
Measurement Specifications and Accuracies
Loop / PFC-PSC
High Current
2 wire test Live – Earth or Phase - Phase, 7A nominal at 230V.
No Trip
3 wire test Live-Earth, 13 mA nominal at 230V, max 5Ω Neutral impedance.
Measurement
Range
Accuracy
System
Voltage Range
System Voltage
Frequency
Over Voltage
Protection
(BS EN 61557-10)

Related product manuals