EasyManua.ls Logo

Socket & See MFT5000 - Page 33

Socket & See MFT5000
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System
Voltage
Range
System Voltage
Frequency
Nominal
Currents
(mA)
Fault /
Touch
Voltage
Trip Time
Accuracy
Over Voltage
Protection
(BS EN 61557-10)
195 – 253 V
ac
50-60 Hz
30, 100,
300, 500
50 V
± (1% +
1ms)
550 V
Function
Display
Range
EN 61557
Measurement
Range
EN 61557
Operating
Uncertainty
Nominal
Values
Insulaon
Resistance
EN 61557-2
0.001 M -
1000M
0.1M – 1000M 1.6%
U
N
= 250 / 500/
1000 V dc
I
N
= 1.0 mA
Loop
Impedance
EN 61557-3
0.01 -
500
1.04 - 470
Hi-I: 4.8%
U
N
= 230/400 V
ac
f = 50/60 Hz
No-Trip: 10.8%
Connuity
EN 61557-4
0.00
20k
0.1 - 10k 12%
4.0 V dc < U
Q
<
24 V dc
R
LO
2.00 I
N
200 mA
RCD
EN 61557-6
T : 5ms –
2000ms
T : 38.2ms –
214.8ms
T : 2.8%
I
N
= 30 / 100 /
300 / 500 mA
I
N
-
I
N
: 15mA – 500mA
I
N :
7.2%
RCD
Operating Ranges and Uncertainties
Test Current
Accuracy
½
+0% -10%
x 1
+10% -0%
x5 (30mA only)
+10% -0%
(Ramp)
± 5% of rated I
N
Accuracy at Applied Test Current
Ramp characteristics: 20% to 110%
of rated IN in 10% steps (300mS
dwell time)
32