Questions and Answers

  • O
    ooliverAug 16, 2025
    What to do if my socomec ITYS 20 kVA UPS shows an output short circuit?
    • M
      michael36Aug 17, 2025
      If the Socomec UPS indicates 'Output Short Circuit', first remove all loads and turn off the UPS. Then, verify both the UPS output and the connected loads for any short circuits. Ensure the short circuit is resolved before restarting the UPS.
  • A
    Andrea WilsonAug 19, 2025
    Why does the BYPASS LED light up on my socomec ITYS 20 kVA when power is on?
    • M
      Mr. Randy BanksAug 19, 2025
      If the 'BYPASS' LED is illuminated on your Socomec UPS even when power is available, it indicates that the inverter is not switched on. To resolve this, press the On-Switch 'I' to activate the UPS.
  • M
    Mikayla VaughnAug 22, 2025
    What to do if my Socomec UPS shows an output or inv overload fault?
    • A
      amanda05Aug 22, 2025
      If your Socomec UPS displays an 'Output Overload' or 'Inv Overload Fault', inspect the connected loads. Remove any non-critical devices to reduce the load. Also, check if any of the connected devices have failed.
  • J
    jeffreybeasleyAug 25, 2025
    Why is the battery LED on and alarm sounding on my socomec ITYS 20 kVA?
    • A
      Anthony KingAug 26, 2025
      If your Socomec UPS is beeping every 4 seconds and the 'BATTERY' LED is lit, it means the input voltage and/or frequency are out of the acceptable range. Check the input power source, building wiring, and input cable. Also, ensure the input breaker is closed.
  • J
    Jeffery KentAug 27, 2025
    What to do if my socomec ITYS 20 kVA shows a heatsink over temperature fault?
    • R
      rarmstrongAug 27, 2025
      If your Socomec UPS displays 'Heatsink Over Temperature Fault', ensure that the UPS is not overloaded, the air vents are not blocked, and the ambient temperature is within the acceptable range. Allow the UPS to cool down for 10 minutes before restarting. If the issue persists, contact your distributor or service center.
  • T
    Taylor LivingstonAug 30, 2025
    Why is my socomec ITYS 20 kVA UPS emergency supply period shorter than expected?
    • A
      ashley57Aug 30, 2025
      If the emergency supply period of your Socomec UPS is shorter than expected, the batteries may not be fully charged or may be defective. Charge the batteries for at least 12 hours, and then check their capacity.
  • A
    Austin PetersonSep 2, 2025
    What does Byp Overload Fault mean on my socomec ITYS 20 kVA UPS?
    • D
      Diane BakerSep 2, 2025
      If your Socomec UPS indicates 'Byp Overload Fault', examine the connected loads. Remove any non-essential devices to lower the load. Additionally, verify if any of the connected devices have malfunctioned.
  • M
    Michael RamirezSep 5, 2025
    What does it mean when my Socomec UPS beeps every second?
    • R
      rsimpsonSep 5, 2025
      If your Socomec UPS is beeping every second, it means the battery is almost empty.
  • N
    Nicholas BarkerSep 7, 2025
    What happens if my socomec ITYS 20 kVA UPS is over charged?
    • K
      kelseybeckSep 8, 2025
      If your Socomec UPS shows 'Over Charge', the UPS will automatically turn off the charger until the battery voltage returns to a normal level.
  • B
    Brian WagnerSep 10, 2025
    Why is my Socomec UPS not showing any signs of power?
    • L
      lewismarySep 10, 2025
      If your Socomec UPS has no indication and no warning tone, even when connected to the mains power supply, check the building wiring and input cable. Also, verify that the input breaker is closed.

Summary

Safety Standards and Precautions

General Safety Procedures

Outlines essential safety procedures, use of qualified technicians, and risks of non-compliance.

Electrical and Battery Safety

Highlights risks of electric shock, battery hazards, and proper connection procedures.

Backfeed Protection Installation

Details the requirement for backfeed protection and its installation to prevent current feedback.

Installation Procedures

Shipping and Moving Guidelines

Provides instructions for safely transporting and moving the UPS unit, emphasizing weight and handling.

Installation Notes and Stability

Covers airflow requirements, ensuring unit stability with mounting brackets or floor anchoring.

Electrical Requirements and Protection

Input Protection Device Specifications

Details recommended input protection devices, cable sizes, and torque values for installation.

Connections and Wiring

Troubleshooting and Support

Problem Resolution Guide

Provides a table of common alerts, problems, causes, and solutions for diagnosing UPS issues.

Advanced Troubleshooting Scenarios

Covers additional fault codes, system errors, and performance issues with their respective solutions.

Technical Specifications

Model and Electrical Specifications

Lists nominal power, input/output phases, mains voltage, frequency, THDI, and output voltage/current.

socomec ITYS 20 kVA Specifications

General IconGeneral
Power Rating20 kVA
Phase3-phase
Frequency50/60 Hz
TopologyDouble Conversion Online
Battery TypeValve Regulated Lead Acid (VRLA)
Form FactorTower
Communication InterfaceRS232, USB
Operating Temperature0 to +40 °C
Relative Humidity0 to 95% (non-condensing)
Input Voltage400/415 V (3Ph+N)
Output Voltage400/415 V (3Ph+N)
Storage Temperature-15 to +50 °C