1 - 3 kVA UPS
ITYS
INSTALLATION AND OPERATING MANUAL EN
www.socomec.com/itys-manuals

Questions and Answers

  • V
    Veronica JonesAug 18, 2025
    What to do if socomec ITY3-TW010B UPS shows power overload?
    • J
      John SpearsAug 18, 2025
      If your socomec UPS indicates a power overload, it means the power requirements of the connected equipment exceed the UPS capacity (more than 105% of nominal). To resolve this, disconnect some equipment from the UPS. The alarm will reset once the overload condition is no longer present.
  • A
    Aaron ParsonsAug 20, 2025
    Why is my socomec ITY3-TW010B in bypass mode?
    • T
      Teresa AdamsAug 20, 2025
      Your socomec UPS may be in Bypass mode due to an overload, a fault, or a received command. When in Bypass mode, the equipment is powered but not protected by the UPS. Check for alarms related to over-temperature, overload, or forced bypass from a dry-in signal.
  • M
    Melissa TaylorAug 23, 2025
    How to switch socomec ITY3-TW010B UPS to battery mode?
    • C
      cwatkinsAug 23, 2025
      The socomec UPS switches to Battery mode automatically when a mains power failure occurs. While in this mode, the UPS is powering your equipment using battery power. It is recommended to prepare your equipment for shutdown.
  • M
    Michael DavisAug 25, 2025
    What causes over-temperature warning on socomec UPS?
    • A
      April YoungAug 26, 2025
      An over-temperature warning on your socomec UPS indicates that the internal temperature is too high. To resolve this, clear any obstructions from the vents, remove any nearby heat sources, and ensure that airflow around the UPS is not restricted. The UPS will continue to operate in its current state while the warning is active.
  • E
    Edward MortonAug 27, 2025
    Why socomec ITY3-TW010B does not provide expected backup time?
    • J
      Jason EscobarAug 27, 2025
      If your socomec UPS isn't providing the expected backup time, the batteries may need charging or servicing. Connect the UPS to mains power for 48 hours to allow the batteries to charge. If the problem persists, contact your service representative.
  • T
    Thomas JacobsonAug 30, 2025
    What to do if socomec UPS shows battery fault?
    • C
      ctaylorAug 30, 2025
      If your socomec UPS displays a battery fault, it means the battery test has failed. This could be due to bad or disconnected batteries, or the battery minimum voltage being reached in Optimize Battery Management cycling mode. Check that all batteries are properly connected. You can start a new battery test. If the condition persists, contact your service representative.
  • D
    Duane MendozaSep 1, 2025
    Why socomec ITY3-TW010B UPS does not start?
    • K
      Karen LewisSep 1, 2025
      If your socomec UPS doesn't start, the input source may not be connected correctly, or the Remote Power Off (RPO) switch might be active, or the RPO connector may be missing. Check the input connections and, if the UPS Status menu displays the 'Remote Power Off' notice, deactivate the RPO input.
  • J
    Jason FloresSep 3, 2025
    What to do for over-temperature fault on socomec ITY3-TW010B?
    • J
      jlewisSep 3, 2025
      If your socomec UPS indicates an over-temperature fault, the internal temperature is too high, causing the UPS to go to bypass or stop. Check the UPS ventilation and the ambient temperature to ensure they are within acceptable limits.
  • L
    Lynn MartinSep 6, 2025
    What does battery low mean on socomec ITY3-TW010B?
    • A
      alexandercardenasSep 6, 2025
      When your socomec UPS indicates 'Battery Low', it means the UPS is operating in Battery mode and the battery is running low. Note that the time to shutdown is approximate and may vary significantly.
  • B
    Benjamin SalinasSep 8, 2025
    What causes emergency power off on socomec UPS?
    • G
      griffithjulieSep 8, 2025
      Emergency power off on your socomec UPS is activated when the RPO (Remote Power Off) is active. Check the RPO connector status to resolve this.

Summary

SAFETY INSTRUCTIONS

Safety of persons

Details precautions and responsibilities regarding personal safety when using the UPS.

Product safety

Covers enclosure rating, electrical protection, installation environment, and storage conditions.

PRODUCT OVERVIEW

LCD panel

Describes the UPS graphical LCD display, its buttons, and LED bar status meanings.

LCD description

Explains the meaning of each area and icon displayed on the UPS LCD screen.

User settings

Lists configurable user settings, available options, and default values for the UPS.

INSTALLATION

Installing the unit

Provides instructions on physical installation, clearances, and connections to power and loads.

OPERATION

Starting the UPS using mains power

Step-by-step guide on how to power on the UPS from the mains supply.

Starting the UPS using battery power

Instructions for starting the UPS directly from its batteries.

UPS MAINTENANCE

TROUBLESHOOTING

Typical alarms and faults

Lists common problems, their possible causes, and recommended actions for resolution.

socomec ITY3-TW010B Specifications

General IconGeneral
Frequency50/60 Hz
Protection LevelIP20
Apparent Power10 kVA
Active Power9 kW
Form FactorTower
Input Voltage400 V
Output Voltage230 V
Phase3-phase
Battery TypeVRLA
Battery RuntimeDepends on load
EfficiencyUp to 96%
Operating Temperature0 to 40°C
Communication InterfaceRS232, USB
TechnologyDouble conversion online