EasyManua.ls Logo

socomec ITY3-TW010B - LCD panel

socomec ITY3-TW010B
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ITYS 1-3 kVA - 551430A - SOCOMEC
21
EN
3.3. LCD panel
The UPS has a ve-button graphical LCD. It provides useful information about the
UPS itself, load status, events, measurements and settings.
ESC
LED bar
LCD
Buttons
Exit Up Down Enter On / Off button
The following table shows the LED bar status and description:
LED BAR COLOR GENERALMEANING
Off Load not suppliedon standby/off etc.
Green Loadprotected by inverter
Green/off Load suppliedand UPS self-tested. (for example, when battery test is in progress)
Green/Yellow Load supplied and preventive alarm present
Yellow Load suppliedwith warning
Yellow/Off Maintain request/in progress
Yellow/Red Load supplied, but no longer protected
Red Load not supplieddue to alarm
Red/Off Load not supplied, but the output will stop in a fewminutes
Yellow/Red/
green
No communication

Related product manuals