24
NETYS RT 1.1-3.3 kVA - Ref.: IOMNETRTXX0B-EN 01
10.6.3 Customized con guration for relay and/or input contacts
Connect Tx to pin 2, Rx to pin 3 and GND-C to pin 5 of the computer’s RS232 port.
In Windows, start the Hyper-Terminal application and proceed to open the specified COM port.
Set the following properties: Baud rate: 2400, Data Bits: 8, Parity: None, Stop Bit: 1, Flow Control: None.
10. COMMUNICATION
• Configuration.
Press <Enter> to display the main menu of the relay card.
1. Press ‘1’ to configure the alarms relative to contacts R1~R6
(Customize Output Relay).
This menu can be used to assign a customized alarm indica-
tion to contacts R1~R6.
Having completed the configuration, shift SW2 to the ON
position to activate the settings. The default settings can be
restored by setting SW2 to OFF.
2. Press ‘2’ to configure the input signal.
The input signal can be used either to shut down the UPS or to
test the batteries. The delay preceding shutdown of the UPS
can be set up to 9999 seconds maximum.
3. Press ‘3’ to configure NO or NC operation of each relay.
Shift SW2 to the ON position to activate the settings.
If SW2 is returned to the OFF position, SW1 can be used to
check the NO or NC position of all the relays.
4. Press ‘0’ to end the configuration session. The system will
prompt you to save the new settings.
Press ‘Y’ to save, ‘N’ to cancel.
UPS Relay Card
Firmware Version: Relay Card V1.4
[1] . Customize Output Relay
[2] . Con gure Input Signal
[3] . Customize Normal Open or Normal Close
[0] . Quit
Please Enter Your Choice >
Con gure Input Signal
[1] . Act as Shutdown or Test: Shutdown
[2] . Input Signal Con rm 3 Seconds
[3] . Delay Before Shutdown 30 Seconds
[0] . Back to Previous Menu
Please Enter Your Choice >
Customize Output Relay
Relay Selected Event
[1] . Relay 1: Summary Alarm
[2] . Relay 2: Power Fail
[3] . Relay 3: Battery Low
[4] . Relay 4: On by-pass
[5] . Relay 5: Overload
[6] . Relay 6: Overtemperature
[0] . Back to Previous Menu
Please Enter Your Choice >
Customize Output Relay
Relay Selected Event
[1] . Relay 1: Normal Close
[2] . Relay 2: Normal Open
[3] . Relay 3: Normal Close
[4] . Relay 4: Normal Open
[5] . Relay 5: Normal Close
[6] . Relay 6: Normal Open
[0] . Back to Previous Menu
Please Enter Your Choice >