Do you have a question about the SODECA CJTHT-40-2/4T-1,5 and is the answer not in the manual?
This document describes the CJTHT, CJTHT/ATEX, and CJTHT/PLUS series of axial extraction units manufactured by SODECA. These units are designed for various ventilation applications, with specific models tailored for ATEX certified environments and those requiring reduced noise levels.
The CJTHT series consists of axial extraction units housed in a soundproofed box, designed for smoke extraction at high temperatures (400°C/2h and 300°C/2h). The CJTHT/ATEX models are specifically certified for use in potentially explosive atmospheres, while the CJTHT/PLUS models integrate a built-in noise reducer for quieter operation. The primary function of these devices is to move air, typically for extraction purposes, in industrial, commercial, or residential settings where robust and reliable ventilation is required, especially in emergency situations involving smoke.
The fans are designed to operate continuously (S1) in temperatures ranging from -20°C to +40°C, with some models suitable for hot climates up to 50°C. They also have a smoke extraction rating (S2) of 300°C/2h and 400°C/2h.
The manual provides extensive tables detailing various models with their respective technical specifications, including:
For example, a CJTHT-90-4T-5,5/PLUS model operates at 1440 r/min, draws 8.40A at 400V, consumes 4.00 kW, has a blade tilting angle of 12°, provides a maximum airflow of 38900 m³/h, generates 84 dB(A) of noise, and weighs approximately 142 kg.
It is crucial to note that CJTHT and CJTHT/PLUS models are not suitable for use in explosive environments. Only CJTHT/ATEX models are certified for such applications.
Installation: Installation must be carried out by a qualified technician familiar with this type of equipment.
General Information: Always check the received products for damage upon unpacking. Damaged products must never be installed. The equipment should only be used for its intended purpose and under the conditions described in the manual. Any defects or malfunctions must be reported to the authorized representative. Before operation, users must read the safety and installation instructions, and for ATEX models, the "General Specifications for ATEX Fans" document.
Safety: Users must not disassemble or modify the equipment. Fingers or objects must not be inserted into protective grilles. In such an event, immediately disconnect power. Never use a damaged power cable. Do not operate the equipment if it is forcibly installed on a curved or unstable surface. Before any inspection or maintenance, ensure the equipment is disconnected from the electrical supply, the safety switch is locked, and all components are at rest. The equipment must not be operated unless properly installed and protected at the inlet and outlet.
Maintenance should only be performed by qualified technicians.
Disposal: Improper disposal of the equipment can cause contamination. The disposal process must comply with the applicable standards and regulations in the country.
Warranty: Incorrect use of the equipment or failure to follow the instructions in this manual will void the warranty.