What should I check if my SOLIS Inverter has no grid voltage?
- LLarry MooreAug 9, 2025
If your SOLIS Inverter indicates no grid voltage, first check the connections and the grid switch. Then, check the grid voltage inside the inverter terminal.
What should I check if my SOLIS Inverter has no grid voltage?
If your SOLIS Inverter indicates no grid voltage, first check the connections and the grid switch. Then, check the grid voltage inside the inverter terminal.
What to do if my SOLIS S5-GR3P20K shows 'Over Temperature'?
If your SOLIS Inverter is showing an 'Over Temperature' error, check the ventilation around the inverter to ensure it's not obstructed. Also, verify whether the inverter is exposed to direct sunlight during hot weather.
What to do if SOLIS S5-GR3P20K LCD has no power?
If your SOLIS Inverter's LCD has no power, check the PV input connections. Also, verify the DC input voltage (single phase >120V, three phase >350V) and ensure that the PV+/- connections are not reversed.
What to do if my SOLIS Inverter shows 'Over DC voltage'?
If your SOLIS Inverter is showing an 'Over DC voltage' error, reduce the number of modules in series.
Why my SOLIS S5-GR3P20K can not start-up?
If your SOLIS Inverter cannot start up, check if the connectors on the main board or power board are securely fixed. Also, check if the DSP connector to the power board is properly connected.
Model | S5-GR3P20K |
---|---|
Rated Output Power | 20kW |
Max DC Input Voltage | 1100 V |
Start-up Voltage | 200 V |
MPPT Voltage Range | 200-850V |
Number of MPPT Trackers | 2 |
Max. Input Current per MPPT | 26A |
Number of DC Inputs per MPPT | 2 |
Max. AC Apparent Power | 22kVA |
Rated Grid Frequency | 50/60 Hz |
THDi | <3% |
DC Switch | Yes |
Protection Degree | IP66 |
Cooling Method | Natural Convection |
Output Voltage | 400 V |
MPPT Range | 200-850V |
Rated Grid Voltage | 230 V / 400 V |
Operating Temperature Range | -25°C to 60°C |
Humidity | 0% - 100% |
Max. DC Input Power | 30000 W |
Grid Voltage Range | 310-480V |
Introduces the Solis S5 three-phase inverters, highlighting DRM and backflow power control for smart grids.
Explains the visual safety symbols (WARNING, NOTE, CAUTION) used in the manual.
Provides critical general safety advice for inverter installation and operation to prevent hazards.
Specifies conditions and guidelines for the inverter's proper and safe usage in installations.
Guides on selecting an appropriate installation site, considering safety and operational factors.
Explains the procedure and dimensions for mounting the inverter on a wall using a bracket.
Details the inverter's electrical connection terminals and the sequence for safe wiring.
Explains the critical grounding methods for effective inverter protection and safety.
Guides on connecting the inverter to the PV array, emphasizing voltage limits and polarity.
Details the process of connecting the inverter to the AC grid, including AC connector assembly.
Recommends OCPD ratings for protecting inverter AC grid connection conductors against overcurrent.
Details connecting smart meters for export power management and consumption monitoring.
Provides step-by-step instructions for safely starting up the inverter and its expected behavior.
Outlines the mandatory sequence for safely shutting down and stopping the inverter.
Explains how to access and view operational data and information from the inverter.
Provides access to detailed technical information for qualified service personnel, requiring a password.
Describes how to view the latest alarm messages logged by the inverter.
Lists advanced configuration options available only to qualified technicians, requiring password entry.
Guides on selecting the grid's reference standard according to local requirements.
Describes the built-in Arc Fault Circuit Interrupter function for DC circuit safety.