EasyManua.ls Logo

SOLIS S5-GR3P20K - Connect grid side of inverter

SOLIS S5-GR3P20K
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
.19..18.
5. Installation5. Installation
A B C D E F
L2
L1
PE
L3
N
Outside-diameters
13~25mm
Cross-section
6~16mm²
60mm
70mm
x
x=9mm
N
L1
L2
L3
5.3.3 Connect grid side of inverter
The steps of AC gird terminal connector for install as follows:
Figure 5.19 AC connector
Figure 5.20 Stripped and bared wire
Figure 5.21 Internal structure of AC connector
Internal of AC connector signs "L1","L2","L3","N" and "PE " five connection
ports (see Figure 5.21). Three live wires are connected the "L1", "L2"and
"L3" terminals respectively; ground wire connects "PE "; neutral wire
connects "N" terminal:
Accessory
AC
connectors
Number
Description
Plastic fixture (Auxiliary installation
Socket element
Adapter
Seal ring
Seal ring (thick) suit for 12-18mm cable
Fastening case
Swivel nut
Figure 5.22 Connected cable
B) Clip plastic fixture (Auxiliary tighten) in socket element , tighten adapter in socket
element, then tighten swivel nut with 3-4Nm torque (see figure 5.23).
Figure 5.23 Assembly AC terminal
C) Connect AC connector with inverter, then tighten AC connector for clockwise (see figure
5.24), until hearing a slight clicking sound indicates connection succeed.
Figure 5.24 AC connector to inverter
For all AC connections, 6-16mm², YJV-0.6/1KV cable is required to be used. Please make sure the
resistance of cable is lower than 1.50hm. If the wire is longer than 20m, preferred to 10-16mm² cable.
Tighten cable with 3.0 mm allen wrench( focus
in dotted box, see figure 5.22). Allen screw is
easy to drop off, don't screw out completely.
*The combination of AC connectors has two seal rings, please refer to different diameters of cable
select corresponding seal ring.
*
Seal ring (thin) suit for 16-21mm cable
PE
A) Stripped the insulation sleeve of cable for 70mm, so that bared copper-cored connector
reaches for 9mm. Cable through nut and sleeve of socket element, insert corresponding
terminals and tighten with allen wrench (see figure 5.22). Torque is 1.8-2.0Nm.

Related product manuals