Solo A3 Detector Tester
Designed to be used only in conjunction
with Solo 330 (332) dispenser
Does not leave residue when used correctly with
Solo 330 (332) Dispenser
Activates detectors quickly
Dissipates rapidly, enabling the detector to be
quickly reset after successful activation
Dispenser conserves aerosol, controls usage
and reduces possibility of misuse
Not using the recommended aerosol can cause
problems and detector damage
Warning
Read CAUTION and Instructions before use.
Aerosols are pressurised containers.
Do not pierce, incinerate or expose to temperatures above 120°F/50°C,
even when empty.
Keep away from sources of heat (including sunlight).
Wear Personal Protection Equipment appropriate to the task and the environment.
Material Safety Data Sheets available on request or online at www.noclimb.com
Solo CO* Aerosol C3
• Suitable for use on CO Fire Detectors
• Designed for use in Solo 330 (332) Dispenser
• See Solo 330 (332) Instructions for use
Warning
Solo CO uses CO in a sufficiently low concentration to be of
minimal risk when used as directed.
CO is colourless and odourless and may be harmful.
Read CAUTION and instructions before use.
*not available in North America
Solo 330 Aerosol Dispenser
Instructions for use
A
Unscrew and remove retainer cup
B Place aerosol canister into cup
C Replace retainer cup & screw upwards
Adjust cup until aerosol activates and
unscrew slightly
D Insert the Solo 330 into Solo pole
Place Solo 330 over detector, ensuring a seal around smoke
chamber.
Press upwards slightly to activate aerosol (no more than 1
second burst).
If the detector has not responded in 10 seconds repeat above
every 10 seconds. Number of total sprays should not exceed 5.
If the detector fails to activate, check equipment and retest.
If the detector does not activate it will require further
investigation.
Maintenance
Excess liquid deposits may be experienced
following extended periods of use. To clean,
use a lint free cloth. Wash the cup with a mild
detergent in warm water and dry thoroughly.
Warning To prevent the possibility of the aerosol discharging while in
transit, loosen retainer cup by unscrewing 2 full turns.
A
D
BC
[ 5 ]
Solo 332
Aerosol
Dispenser
available
for larger
detectors
[ 4 ]
Downloaded from Elcodis.com electronic components distributor