Quick Start Guide for ST600 Series Frequency Inverters Important Function Parameter Settings
11
5 Important Function Parameter Settings
Only a few common function parameters and typical values are briefly described below.
"○" indicates that the value of the parameter can be changed when the VFD is in stop or operating mode.
"◎" indicates that the value of the parameter cannot be changed while the VFD is in operation.
"●" indicates that the value of the parameter is recognized and saved, but cannot be changed.
(The VFD automatically checks parameter changes and restricts them to prevent invalid settings.)
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: Closed-loop vector control mode
Channel Of Running
Commands
0: Keypad
1: Terminal
2: Communication
Communication Mode Of
Running Commands
0: Modbus/Modbus TCP
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/PROFINET/ Ethernet IP
4: Programmable expansion card
5: Wireless communication card
6: Reserved
Note: The options 0 (for Modbus TCP), 1, 2, 3, 4
and 5 are add-on functions, valid only when config-
ured with related expansion cards.
Max (P00.04; 10)–630.00Hz
Upper Limit Of Running
Frequency
P00.05–P00.03 (Max. output frequency)
Lower Limit Of Running
Frequency
0.00Hz–P00.04 (Upper limit of running frequency)
Channel to Set
Frequency Reference
Value A
0: Keypad
1: AI1
2: AI2
3: AI3