Quick Start Guide for ST600 Series Frequency Inverters Possible Errors and Solutions
17
6 Possible Errors and Solutions
Note: Our error code scheme is being upgraded. Some products use the old scheme and the others use the new
one, which are listed in "Error code display".
[1] Inverter Unit U Phase
Protection
Acceleration is too fast;
IGBT module is damaged;
Malfunction due to interference; wires
are poorly connected;
To-ground short-circuit occurred
Increase acceleration time;
Replace the power unit;
Check the wires;
Check for sources of strong interfer-
ence in the vicinity of the peripheral
device
[2] Inverter Unit V Phase
Protection
[3] Inverter Unit W
Phase Protection
[4] Overcurrent During
Acceleration
Acceleration is too fast;
Grid voltage is too low;
VFD power is too small;
Load transient or exception occurred;
To-ground short-circuit or output
phase loss occured;
Strong external interference;
Overvoltage stalling protection is not
enabled
Increase the ACC/DEC time;
Check the input power;
Select a VFD with larger power;
Check if the load is short-circuited (to-
ground short-circuit or line-to-line
short-circuit) or the rotation is not
smooth;
Check the output wiring;
Check for sources of strong interfer-
ence;
Check the setup of related function
codes.
[5] Overcurrent During
Deceleration
[6] Overcurrent During
Constant Speed
Running
[7] Overvoltage During
Acceleration
Deceleration is too short;
Exception occurred at the input volt-
age;
Large energy feedback;
Lack of braking units;
Dynamic braking is not enabled, and
the deceleration time is too short.
Check the input power;
Check if the load deceleration time is
too short; or if the motor starts up dur-
ing rotation;
Install dynamic braking units;
Check the settings of related function
codes
[8] Overvoltage During
Deceleration
[9] Overvoltage During
Constant Speed
[10] Bus Undervoltage
Error
Grid voltage is too low;
Overvoltage stalling protection is not
enabled
Check the grid input power;
Check the setup of related function
codes
Grid voltage is too low;
Rated motor current is set incorrectly;
The motor stalls, or the load jumps vi-
olently
Check the grid voltage;
Reset the rated motor current;
Check the load and adjust the torque
boost
Acceleration is too fast;
Increase acceleration time;