Quick Start Guide for ST600 Series Frequency Inverters Possible Errors and Solutions
18
The motor restarts during rotation;
Grid voltage is too low;
Load is too large;
Power is too low;
Avoid restart after stop;
Check the grid voltage;
Select a VFD with larger power;
Select a suitable motor
[13] Phase Loss On
Input Side
Phase loss or intense fluctuation oc-
curred to R, S and T input
Check the input power;
Check installation wiring
[14] Phase Loss On
Output Side
Phase loss occurred to U, V, W output
(or the three phases of the motor are
asymmetrical)
Check the output wiring;
Check the motor and cable
[15] Rectifier Module
Overheating
Air duct is blocked or fan is damaged;
Ambient temperature is too high;
Long-term overload
Ventilate the air duct or replace the
fan;
Lower the ambient temperature
[16] Inverter Module
Overheating
[18] Modbus/Modbus
TCP Communication
Error
Baud rate is set incorrectly;
Communication line error;
Communication address error;
Communication suffers from strong in-
terference
Set a suitable baud rate;
Check the wiring of communication
interfaces;
Set a suitable communication ad-
dress;
Replace or change the wiring to im-
prove anti-interference capacity
[20] Motor Autotuning
Error
Motor capacity does not match with
the VFD capacity, this error may occur
easily if the difference between them
is exceeds five power classes;
Motor parameters are set incorrectly;
The parameter settings obtained via
autotuning deviate sharply from the
standard standards;
Autotuning timeout
Select a different VFD model, or ena-
ble V/F control mode;
Set the correct motor type and name-
plate parameters;
Empty the motor load and restart au-
totuning;
Check the motor wiring and parame-
ter setup;
Check whether the frequency upper
limit is larger than 2/3 of the rated fre-
quency
[34] Speed Deviation
Error
Load is too heavy, or stalling occurred
Check the load to ensure it is suitable,
increase the detection time;
Ensure that the control parameters
are set correctly
Control parameters of synchronous
motor is set improperly;
The parameter settings obtained via
autotuning are inaccurate;
Check the load to ensure it is suitable,
Ensure that the control parameters
are set correctly;