EasyManua.ls Logo

Sourcetronic ST600 - Page 27

Sourcetronic ST600
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Quick Start Guide for ST600 Series Frequency Inverters Energy Efficiency Data
26
Table A-2 Power Loss and IE Class of SP Model VFDs
Product Model
Relative Loss (%)
Standby
Loss (W)
IE
Class
(0;25)
(0;50)
(0;100)
(50;25)
(50;50)
(50;100)
(90;50)
(90;100)
ST600SP-004G3
1.52
1.76
2.33
1.50
1.77
2.36
1.70
2.44
6
IE2
ST600SP-5R5G3
0.94
1.27
2.07
1.01
1.38
2.33
1.53
2.60
8
IE2
ST600SP-7R5G3
0.76
0.96
1.53
0.75
0.97
1.60
0.98
1.75
10
IE2
ST600SP-011G3
0.61
0.84
1.55
0.61
1.04
1.97
0.99
2.16
10
IE2
ST600SP-015G3
0.56
0.78
1.42
0.56
0.78
1.46
0.80
1.60
10
IE2
ST600SP-018G3
0.51
0.70
1.26
0.52
0.74
1.38
0.71
1.36
14
IE2
ST600SP-022G3
0.58
0.80
1.37
0.64
0.87
1.59
0.94
1.71
11
IE2
ST600SP-030G3
0.53
0.68
1.32
0.64
0.73
1.54
0.83
1.65
14
IE2
ST600SP-037G3
1.02
1.24
1.92
1.10
1.38
2.16
1.49
2.37
20
IE2
ST600SP-045G3
0.92
1.12
2.02
1.03
1.26
1.86
1.38
1.95
21
IE2
ST600SP-055G3
0.53
0.73
1.38
0.61
0.83
1.47
0.88
1.47
21
IE2
ST600SP-075G3
0.44
0.61
1.12
0.51
0.69
1.29
0.76
1.42
22
IE2
ST600SP-090G3
0.42
0.59
1.15
0.47
0.65
1.29
0.90
1.48
25
IE2
ST600SP-110G3
0.66
0.86
1.53
0.79
1.01
1.77
1.12
1.93
28
IE2
Table A-3 Rated Specifications of Standard & SP Model VFDs
Product Model
Apparent
Power
(Kva)
Rated
Output
Power (Kw)
Rated
Output
Current (A)
Max. Working
Temperature
(°C)
Rated Power
Frequency (Hz)
Rated Power
Voltage (V)
ST600-1R5G3
2.4
1.5
3.7
50°C, derate
1% for every
increase of
1°C if the tem-
perature ex-
ceeds 40°C
50Hz/60Hz, al-
lowed range:
47-63Hz
3PH 380V
ST600-2R2G3
3.2
2.2
5
ST600/ST600SP-004G3
6.2
4
9.5
ST600/ST600SP-5R5G3
9.2
5.5
14
ST600/ST600SP-7R5G3
12.2
7.5
18.5
ST600/ST600SP-011G3
16.4
11
25
ST600/ST600SP-015G3
21.0
15
32
ST600/ST600SP-018G3
25.0
18.5
38
ST600/ST600SP-022G3
29.6
22
45
ST600/ST600SP-030G3
39.4
30
60

Other manuals for Sourcetronic ST600