IM-S21-01 CH Issue 7
2
1. General safety information
Safe operation of these products can only be guaranteed if they are properly
installed, commissioned, used and maintained by qualified personnel (see
Section 1.11 ) in compliance with the operating instructions. General installation and
safety instructions for pipeline and plant construction, as well as the proper use of
tools and safety equipment must also be complied with.
Warning - Laminated gaskets
The metal foil sheet used to reinforce gaskets is very thin and sharp. Care should be taken
when handling to avoid the possibility of cuts or lacerations to fingers or hands.
1.1 Intended use
Referring to the Installation and Maintenance Instructions, name-plate and Technical
Information Sheet, check that the product is suitable for the intended use/application.
The products listed below comply with the requirements of the European Pressure
Equipment Directive 97/23/EC and carry the mark when so required. The products fall
within the following Pressure Equipment Directive categories:
Group 2 Group 2
Product
Gases Liquids
BX, BXRA, BM, BMRA, BMF, BMFRA, SB and SBRA SEP SEP
KA, KB, KC, KX, KY31 and KY33 SEP SEP
KA, KB, KC, KX and KY43
DN15 - 32 SEP SEP
DN40 - 50 1 SEP
KA, KB, KC, KX and KY51
DN15 - 40 SEP SEP
DN50 1 SEP
KA61, KA63 and KC63 DN15 - 32 SEP SEP
KA and KC63 DN40 - 50 1 SEP
NS and NSRA 1 SEP
i) The products have been specifically designed for use on steam, water and other
non-hazardous fluids which are in Group 2 of the above mentioned Pressure
Equipment Directive. The products’ use on other fluids may be possible but, if
this is contemplated, Spirax Sarco should be contacted to confirm the suitability
of the product for the application being considered.
ii) Check material suitability, pressure and temperature and their maximum and
minimum values. If the maximum operating limits of the product are lower than
those of the system in which it is being fitted, or if malfunction of the product
could result in a dangerous overpressure or overtemperature occurrence, ensure
a safety device is included in the system to prevent such over-limit situations.
iii) Determine the correct installation situation and direction of fluid flow.
iv) Spirax Sarco products are not intended to withstand external stresses that may
be induced by any system to which they are fitted. It is the responsibility of the
installer to consider these stresses and take adequate precautions to minimise
them.
v) Remove protection covers from all connections before installation.