I-Line™ Combo Switchboards 80043-808-02 Rev. 02
Appendix 2: Accessory Kits—Circuit Breaker Lug Kits 03/2017
58
ENGLISH
Circuit Breaker Lug Kits
Versa-Crimp
®
and Versatile™ kits can be field installed.
Table 12: Versa-Crimp Lugs and Versatile Compression Lug Kits
1
Aluminum Wire Range
2
Versa-Crimp
Tool
Copper Wire Range
2
Versa-Crimp
Tool
VC100FA
VC100FD
8–1/0
8.36–53.5 mm
2
VC-6
CVC100FA
CVC100FD
6–1/0 CU
13.3–53.5 mm
2
VC-6 Series
VC250KA3
4–300 kcmil
21.1–151 mm
2
CVC250KA3
2/0–300 kcmil CU
67.4–151 mm
2
VC250KA35
250–350 kcmil
127–177 mm
2
CVC400LA3
4–300 kcmil CU
21.1–151 mm
2
VC400LA35
250–350 kcmil
127–177 mm
2
CVC400LA5
CVC600MA5
250–500 kcmil CU
127–253 mm
2
VC400LA3
4–300 kcmil
21.1–151 mm
2
—
VC400LA5
2/0–500 kcmil
67.4–253 mm
2
VC400LA7
500–750 kcmil AL
253–380 mm
2
500 kcmil CU
253 mm
2
VC-6 FT
VC-8
VC400LA7
2/0–500 kcmil
67.4–253 mm
2
VC-6 Series
—
VC800MA7
500–750 kcmil AL
253–380 mm
2
500 kcmil CU
253 mm
2
VC-6 FT
VC-8
LV426988 # 8–1/0 AWG
3
LV426986 # 6–1/0 AWG
3
LV426989 # 8–1/0 AWG
3
LV426987 # 6–1/0 AWG
3
YA060HD # 6–#2 AWG
3
CYA060HD # 6–1/0 AWG CU
3
YA150HD # 1–4/0 AWG CYA150JD # 4–2/0 AWG CU
YA150JD # 1–3/0 AWG CYA150HD # 6–1/0 AWG CU
YA250J35 3/0–350 kcmil CYA250J3 1/0–350 kcmil CU
1
Always ensure compression lugs are installed in switchboards that will provide wire bending space in
accordance with NEC Article 312.6, 2011 Edition.
2
Unless otherwise specified, wire sizes apply to both aluminum and copper conductors.
3
Use crimp tools according to the instructions provided with each lug kit.