80043-808-02 Rev. 02 I-Line™ Combo Switchboards
03/2017 Appendix 2: Accessory Kits—Equipment Ground Bar Kits, Extension Kits
57
ENGLISH
l
Table 11: Compression Lug Kits for MG, MJ, L-, P-Frame Circuit Breaker
1
Aluminum Wire Range
2
Versa-
Crimp
®
Tool
Copper Wire Range
2
Versa-Crimp
Tool
YA250P3
2/0–300 kcmil
67.4–151 mm
2
3
CYA400P5
4/0–500 kcmil CU
107–253 mm
2
3
YA300P5
4/0–500 kcmil
107–253 mm
2
CYA600P5
4/0–500 kcmil CU
107–253 mm
2
YA400P3
2/0–300 kcmil
67.4–151 mm
2
CYA800P7
500–750 kcmil CU
253–380 mm
2
YA400P7
500–750 kcmil
253–380 mm
2
——
YA600P5
4/0–500 kcmil
107–253 mm
2
——
YA800P7
500–750 kcmil
253–380 mm
2
——
YA400L31K3
4
#4–300 kcmil
21–151 mm
2
3
CYA400L31K3
4
2/0–300 kcmil
67.4–151 mm
2
3
YA600L32K3
4
CYA600L32K3
4
YA400L51K3
4
2/0–500 kcmil
67.4–253 mm
2
CYA400L51K3
4
250–500 kcmil
127–253 mm
2
YA600L52K3
4
CYA600L52K3
4
YA400L71K3
4
500–750 kcmil
253–380 mm
2
——
1
Always ensure compression lugs are installed in switchboards that will provide wire bending space in
accordance with NEC Article 312.6, 2011 Edition.
2
Unless otherwise specified, wire sizes apply to both aluminum and copper conductors.
3
Use crimp tools according to the instructions provided with each lug kit.
4
For L-frame circuit breakers only.
80043-808-01.book Page 57 Wednesday, March 22, 2017 12:31 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Square D I-Line and is the answer not in the manual?

Square D I-Line Specifications

General IconGeneral
Bus MaterialAluminum or Copper
Voltage Rating600V AC
Current RatingUp to 1200A
EnclosureNEMA 1
Poles2, 3
Interrupting Rating200 kA (depending on the specific model and installed breakers)