Table 2. Index List
Index Description
0 - 99 Sengs Values, see Table 3.
90 - 95 Reserved.
96 Command – Restart FIS. Entering “01” will cause FIS to restart.
97 Firmware – Entering “01” will display “FE” followed by two pairs of digits followed by “FE”. For example,
if the rmware was 0609 the controller will display “FE” “06” “09” “FE”.
98 Command – Restart auto conguraon. Entering “01” sets the Control Box to “A1” keeping all previous
values and then re-learns the encoder count.
99* Command – Lock. Entering “01” will lock all value inputs except this index. This prevents inadvertent
changes to input values. Values may be unlocked by entering “00” in this index.
Table 3. Settings
Index Min.
Value
Max
Value
Defaults
Single Dual
0 1 99* Open
Speed
Open Speed is the speed used during normal operaon
in the opening state (02).
This speed is set to change how long it takes the door
to open.
This parameter sets the target speed seng. Other
parameters like open torque, open startup torque, open
startup length, and open acceleraon as well as door
properes like fricon, door length, and door weight
aect door speed.
99 99
1 1 99* Close
Speed
Close Speed is the speed used during normal operaon in the
closing state (07).
This speed is set to change how long it takes the door
to close.
This parameter sets the target speed seng. Other
parameters like Close Torque, Close Startup Torque, Close
Startup Length, and Close Acceleraon as well as door
properes like fricon, door length, and door weight aect
door speed.
35 25
2 1 99* Open
Check
Speed
Open Check Speed is the speed used during normal
operaon in the open check state (04) prior to arriving at
full open.
This speed is set to determine how fast the door arrives at
full open aer open speed.
This parameter sets the target speed seng. Other
parameters like open check torque, open acceleraon,
and open braking as well as door properes like fricon,
door length, and door weight aect door speed.
10 10
Table 3 Settings continued next page.
NOTE: With the iQ Toolbox, the Max Values are 125.