iQ Control Box
12 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
Copyright 2019, Stanley Access Technologies, LLC.
All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
Index Min
Value
Max
Value
Description Defaults
Single Dual
20 0 1 Hold Beam Type 00 - Non-monitored Hold Beam
01 - Monitored Hold Beam
Selects the hold beam type to be used for
monitored or non-monitored applicaons.
For Monitored Hold Beams: Photobeam Pro or
Optex OSC12CT refer to wiring diagrams
per applicaon.
1 1
21 1 50 Lock Delay This allows the lock to mechanically unlock
before door moon. Lock Delay in 0.1 second
increments.
1 1
22 0 99 Open Stop Distance Distance from full open that the door will stop.
This will be in 0.25” increments.
4 4
23 1 99 Close Check Speed Close Check Speed is the speed used during
normal operaon in the close check state (09)
prior to arriving at full closed.
This speed is set to determine how fast the
door arrives at full closed aer close speed.
This parameter sets the target speed seng.
Other parameters like close check torque, close
acceleraon, and close braking as well as door
properes like fricon, door length, and door
weight aect door speed.
8 8
24 0 1 Access Control Pro
Enabled
Inside sensor lockout funcon.
00= OFF
01= ON
When set to 01-On, the interior acvaon in-
put is inhibited if the exterior acvaon input
is acve. Acvaon override can be
accomplished through TB2 pin 9 and 10.
0 0
25 0 5 Close Press Close Press aects how the doors press
together at full closed. If the value selected is
0, the door does not press at the closed
posion. A value of 1 will have a soer release
of motor energy and a value of 5 will be a
quicker release.
2 2
27 1 99 Lock Release Torque Lock Release Torque is the torque used on
lock release state. A closed posion switch is
required, connected to TB-5.
This parameter sets the maximum current
available to the motor which is directly
proporonal to the door force.
20 20
28 1 60 Close Check
Obstrucon Time
Close Check Obstrucon Time is the amount of
me in increments of 0.025s the door
applies force when almost stopped or stopped
when the controller indicates a state of “09”.
Before increasing this parameter, check
mechanical issues, and speed and torque
parameter sengs.
50 50
Table 3. Settings (continued)