Index Min
Value
Max
Value
Description Defaults
Single Dual
20 0 1 Hold Beam Type 00 - Non-monitored Hold Beam
01 - Monitored Hold Beam
Selects the hold beam type to be used for
monitored or non-monitored applicaons.
For Monitored Hold Beams: Photobeam Pro or
Optex OSC12CT refer to wiring diagrams
per applicaon.
1 1
21 1 50 Lock Delay This allows the lock to mechanically unlock
before door moon. Lock Delay in 0.1 second
increments.
1 1
22 0 99 Open Stop Distance Distance from full open that the door will stop.
This will be in 0.25” increments.
4 4
23 1 99 Close Check Speed Close Check Speed is the speed used during
normal operaon in the close check state (09)
prior to arriving at full closed.
This speed is set to determine how fast the
door arrives at full closed aer close speed.
This parameter sets the target speed seng.
Other parameters like close check torque, close
acceleraon, and close braking as well as door
properes like fricon, door length, and door
weight aect door speed.
8 8
24 0 1 Access Control Pro
Enabled
Inside sensor lockout funcon.
00= OFF
01= ON
When set to 01-On, the interior acvaon in-
put is inhibited if the exterior acvaon input
is acve. Acvaon override can be
accomplished through TB2 pin 9 and 10.
0 0
25 0 5 Close Press Close Press aects how the doors press
together at full closed. If the value selected is
0, the door does not press at the closed
posion. A value of 1 will have a soer release
of motor energy and a value of 5 will be a
quicker release.
2 2
27 1 99 Lock Release Torque Lock Release Torque is the torque used on
lock release state. A closed posion switch is
required, connected to TB-5.
This parameter sets the maximum current
available to the motor which is directly
proporonal to the door force.
20 20
28 1 60 Close Check
Obstrucon Time
Close Check Obstrucon Time is the amount of
me in increments of 0.025s the door
applies force when almost stopped or stopped
when the controller indicates a state of “09”.
Before increasing this parameter, check
mechanical issues, and speed and torque
parameter sengs.
50 50