INSTALLATION
INSTALLATION
11.8 Condensate drain
26�03�01�1127
1
< 889 (35")
2
3
4
5
6
1 Condensate drain or
2 Drain pan connected to drain
3 T&P valve
4 Cold water connection
5 Hot water connection
6 Condensate spillover
The condensate drain is located on the side of the water heater.
This is where you can connect a drain hose.
When installing the unit outdoors, the condensate can drain off
freely.
For indoor installation, the condensate can be routed into a floor
drain or routed through the wall up to 889mm (35") (see diagram
above).
If required, install a condensate pump.
To ensure the condensate drains correctly, never kink
the hose.
11.9 Water connection
The water connection must be carried out by a qualified licensed
plumber.
The cold water connection must comply with DIN1988 [or state
and local codes]
» Prior to installing the water heater, flush the line thoroughly.
H
M
C
1
5
6
2
3
4
Cold water
7
8
9
10
Hot water
13
14
12
11
26_03_01_1123
15
1 Vacuum breaker
2 Hot water connection (Union adaptor to 3/4")
3 Mixing valve (optional, supplied by installer)
4 Connection for T&P valve ¾"
5 T&P valve ¾", 0.69 MPa @99 °C (100 psi @210 °F) (supplied
with unit)
6 0.551 MPa (80 psi) relief valve (optional, supplied by
installer)
7 Expansion tank (optional, supplied by installer)
8 Straight-through shut-off valve (supplied by installer)
9 Check valve (optional, supplied by installer)
10 0.48 MPa (70 psi) pressure reduction valve (optional,
supplied by installer)
11 Cold water connection (with Union adaptor to 3/4")
12 Condensate drain (elbow supplied with unit)
13 Drain valve (supplied by installer)
14 Drain pan (supplied by installer)
15 Condensate spillover
» Remove the protective plastic caps from the connectors.
» Connect the plumbing.
Risk of damage through corrosion
To protect against the risk of corrosion, make the
connection with flat gaskets.
» Insulate the hot water line against heat loss.
» Install a drain valve at the lowest point of the cold water
supply.
Install a 0.48 MPa (70 psi) pressure reducing valve on the cold
water inlet.