WWW.STIEBEL-ELTRON.COM LWZ 170 E PLUS / LWZ 370 PLUS | 21
INSTALLATION
Settings
12.2 Read-out menu
With the read-out menu, you can call up some values for more
detailed information on the function of the appliance. Values and
settings cannot be changed in the read-out menu.
Press menu in standard mode.
The settings menu is displayed ("SET").
26�04�15�0064
Press plus or minus to switch to the read-out menu.
26�04�15�0071
Press menu to enable the read-out menu.
26�04�15�0072
Use plus or minus in the read-out menu to move to the required
parameter.
26�04�15�0073
1 2
Parameter Description of the actual value Unit
01 Room temperature °C
02 Outside temperature (captured by the outside temper-
ature sensor)
o
C
03 Bypass status (ON = Bypass damper open,
OFF = Bypass damper closed)
04 Frost protection status (ON = Frost protection enabled,
OFF = Frost protection disabled)
05 Supply air duct pressure Pa
06 Extract air duct pressure Pa
07 Air flow rate of supply air fan m
3
/h
08 Air flow rate of extract air fan m
3
/h
Press R twice to return to standard mode.
2 x
26�04�15�0074
If no key is pressed for 5 minutes, the appliance returns automat-
ically to standard mode.
12.3 Service menu
In the service menu, you can view the last 10 fault messages.
In the case of blocking faults, the settings menu and the read-out
menu are blocked and only the service menu can be accessed.
Pressing menu opens the service menu.
Viewing the service menu
Press menu in standard mode. The settings menu is
displayed.
26�04�15�0064
Press plus or minus to switch to the read-out menu.
26�04�15�0057
Press menu to enable the service menu.