INSTALLATION
Maintenance
13. Maintenance
WARNING Electrocution
In the event of damage to the power cable this must
always be replaced by a qualified contractor authorised
by the manufacturer, using original spare parts.
Maintenance by the qualified contractor includes the cleaning of
the cross-countercurrent heat exchanger and the fans.
Subject to runtime, this maintenance work should be carried out
every 3 years.
Switch off the appliance by pressing the minus key for
5seconds.
Disconnect the power supply.
Open the filter door.
Extract the filters. Make a note of how the filters were fitted.
26�04�15�0042
Remove the front cover.
26�04�15�0043
Carefully remove the heat exchanger from the appliance.
Avoid damaging the foam parts in the appliance.
26�04�15�0047
Use a commercially available vacuum cleaner to remove dust
and other loose dirt particles from the intake and discharge
surfaces.
If required, clean the heat exchanger with warm water
(max.55 °C) and a commercially available detergent. Never
use solvents.
Afterwards flush the heat exchanger with water.
Remove the plug-in connections from the back of the display
cover.
26�04�15�0044
Undo both screws securing the display cover to the
appliance.
26�04�15�0046
Remove the display cover.
Disconnect the 4 pressure hoses and 3 plug-in connections
from the PCB.