INSTALLATION
SAFETY
INSTALLATION
7. Safety
7.1 General safety instructions
- Only a qualified contractor should carry out installation,
commissioning, maintenance and repair of the appliance.
- We guarantee trouble-free operation and operational reli-
ability only if the original accessories and spare parts intend-
ed for the appliance are used.
7.2 Instructions, standards and regulations
Note
Observe all applicable national and regional regulations
and instructions.
8. Equipment description
The appliance protects the heating water lines against freezing up.
The integral frost protection circuit starts the circulation pump in
the heat pump circuit automatically at a condenser temperature
of 8 °C, and thereby ensures circulation in all water-carrying sec-
tions. If the temperature inside the buffer cylinder drops, the heat
pump starts automatically no later than when the temperature
falls below +5 °C.
8.1 Standard delivery
Delivered with the appliance:
- Wiring diagram
- Condensate drain hose
8.2 Accessories
8.2.1 Required accessories
Description
Heat pump manager with wall mounting casing, WPMW 3
8.2.2 Further accessories
Description
Wall mounting support WK-WPL
T-support SK-WPL
Mounting bracket MK-WPL 10 AC(S)
Hydraulic module HSBB 2.1
Pressure hoses DN 25
Remote control for heating systems FEK
Remote control for heating systems FE7
Starting current limiter 25 A
9. Preparations
The appliance is designed for siting in front of a wall. If the ap-
pliance is installed in an open space or on a roof, protect the air
intake side by erecting a wall to shield it against the wind.
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
9.1 Acoustic emissions
On the air intake and air discharge sides, the appliance is louder
than on the enclosed sides. Please therefore observe the informa-
tion below.
For the sound power level, see chapter “Specification/Data table”.
Ensure that the air intake direction is the same as the main
wind direction. Air should not be drawn in against the wind.
Never direct the air intake or discharge towards noise sensi-
tive rooms of the house (e.g. bedrooms).
Lawn areas and shrubs contribute to the reduction of noise. For
this, observe the minimum clearances in the following figure:
Noise can also be reduced through dense palisades if these are
installed around the appliance. Observe the minimum clearances.