32 | WPL 10 ACS WWW.STIEBEL-ELTRON.COM
INSTALLATION
SPECIFICATION
13.8 Details on energy consumption
Product data complies with EU regulations relating to the Directive on the ecodesign of energy related products (ErP).
WPL 10 AC WPL 10 ACS
230236 227995
Manufacturer STIEBEL ELTRON STIEBEL ELTRON
Energy efficiency category for central heating in moderate climates for medium temperature applications A+ A+
Energy efficiency category for central heating in moderate climates for low temperature applications A+ A+
Rated heating output in moderate climates for medium temperature applications kW 6 5
Rated heating output in moderate climates for low temperature applications kW 7 7
Energy efficiency for central heating in moderate climates for medium temperature applications % 115 110
Energy efficiency of central heating in moderate climates for low temperature applications % 145 139
Energy consumption in moderate climates for medium temperature applications kWh/a 4036 3994
Energy consumption in moderate climates for low temperature applications kWh/a 3865 3902
Rated heating output in colder climates for medium temperature applications kW 9 11
Rated heating output in colder climates for low temperature applications kW 10 10
Rated heating output in warmer climates for medium temperature applications kW 3 3
Rated heating output in warmer climates for low temperature applications kW 4 4
Energy efficiency of central heating in colder climates for medium temperature applications % 100 87
Energy efficiency of central heating in colder climates for low temperature applications % 118 113
Energy efficiency of central heating in warmer climates for medium temperature applications % 125 81
Energy efficiency of central heating in warmer climates for low temperature applications % 161 157
Energy consumption in colder climates for medium temperature applications kWh/a 8717 11633
Energy consumption in colder climates for low temperature applications kWh/a 8530 8664
Energy consumption in warmer climates for medium temperature applications kWh/a 1250 2105
Energy consumption in warmer climates for low temperature applications kWh/a 1238 1198
Sound power level external dB(A) 59 59
13.9 Data table
Output details apply to new appliances with clean heat exchangers.
The power consumption of the integral auxiliary drives is stated as a maximum and may vary, subjectto operating point.
The power consumption of the integral auxiliary drives is already included in the output details of the heat pump, as specifi ed by the
EN 14511.
WPL 10 AC WPL 10 ACS
230236 227995
Outputs to EN 14511
Output at A-7/W35 (EN 14511) kW 5.11 4.94
Output at A2/W35 (EN 14511) kW 6.74 6.53
Output at A7/W35 (EN 14511) kW 7.83 7.72
Output at A10/W35 (EN 14511) kW 8.29 8.49
Heating output at A7/W45 (EN 14511) kW 7.26 7.22
Refrigerating capacity at A35/W7 kW 6.22 6.39
Cooling capacity at A35/W18 kW 9.12 9.31
Power consumption
Power consumption, emergency/booster heater kW 8.8 6.2
Power consumption, fan heating max. kW 0.11 0.11
Power consumptions to EN 14511
Power consumption at A-7/W35 (EN 14511) kW 1.67 1.73
Power consumption at A2/W35 (EN 14511) kW 1.92 1.94
Power consumption at A7/W35 (EN 14511) kW 2.03 2.05
Power consumption at A10/W35 (EN 14511) kW 2.06 2.11
Power consumption at A7/W45 (EN 14511) kW 2.25 2.26
Power consumption, cooling at A35/W18 kW 3.16 3.26
Power consumption - cooling at A35/W7 kW 2.56 2.61
Coefficients of performance to EN 14511
Coefficient of performance at A-7/W35 (EN 14511) 3.06 2.86
Coefficient of performance at A2/W35 (EN 14511) 3.51 3.37
Coefficient of performance at A7/W35 (EN 14511) 3.86 3.77
Coefficient of performance at A10/W35 (EN 14511) 4.02 4.02
Coefficient of performance at A7/W45 3.22 3.19