INSTALLATION
Commissioning
22 | WPL-A Premium www.stiebel-eltron.com
12.3.1 Function test without buffer cylinder
Note
If the appliance is operated solely through the WPM heat
pump manager, and an external pump that is not con-
trolled by the WPM is used as a heating circuit pump, you
will have to adjust the heating circuit pump manually.
For systems without a buffer cylinder, one or more heating cir-
cuits in the system must remain open. The open heating circuit(s)
must be installed in the lead room (room in which the external
programming unit is installed, e.g. living room or bathroom). The
lead room can be individually controlled using the external pro-
gramming unit, or indirectly by adjusting the heating curve or
activating room influence.
f Operate the appliance in heating mode.
f When designing underfloor heating in the lead room, ob-
serve our recommendations. The table applies if individual
room control is installed.
WPL-A 05 HK 230
Premium
WPL-A 07 HK 230
Premium
Minimum flow rate of heat pump
l/h 640 640
Minimum water content of the open heating circuits during
operation without buffer cylinder
l 20 20
Composite pipework 16 x 2mm / installation spacing 10cm
Lead room floor area
21 21
Number of circuits
nxm 3x70 3x70
Composite pipework 20 x 2.25mm / installation spacing 15cm
Lead room floor area
21 21
Number of circuits
nxm 2x70 2x70
Buffer cylinder always required
no no
Buffer cylinder volume in relation to product range
l 80-200 80-200
Activate the integral emergency/booster heater
Yes Yes
f Fully open the heating circuit(s) in the lead room.
f Close all other heating circuits.
f If an overflow valve is installed in the heating system, close
this valve.
f Adjust the parameters.
Parameter Setting
MINIMUM PUMP RATE (COMMISSIONING/ CHARGING
PUMP CONTROL / STANDBY/ TYPE OF CONTROL)
OFF
MAXIMUM PUMP RATE (COMMISSIONING/ CHARGING
PUMP CONTROL / STANDBY/ TYPE OF CONTROL)
ON
f Check the current flow rate.
Parameter
WP WATER FLOW RATE (INFO/ HEAT PUMP/ PROCESS DATA)
f Compare the value with the minimum flow rate (see chapter
"Specification/ Data table").
Minimum flow rate has been reached
No further measures required.
f Reset the parameters to their original values.
Parameter Setting
MINIMUM PUMP RATE (COMMISSIONING/ CHARGING
PUMP CONTROL / STANDBY/ TYPE OF CONTROL)
ON
MAXIMUM PUMP RATE (COMMISSIONING/ CHARGING
PUMP CONTROL / STANDBY/ TYPE OF CONTROL)
OFF
Minimum flow rate has not been reached
If the specified flow rate is not met, take suitable measures to
achieve the flow rate.
f Open the heating circuit permanently in another room.
f Check the current flow rate.
f If the minimum flow rate is not reached, repeat these steps.
f Set the overflow valve correctly.
12.3.2 Function test with buffer cylinder
f Operate the appliance in heating mode.
f Adjust the parameters.
Parameter Setting
MINIMUM PUMP RATE (COMMISSIONING/ CHARGING
PUMP CONTROL / STANDBY/ TYPE OF CONTROL)
OFF
MAXIMUM PUMP RATE (COMMISSIONING/ CHARGING
PUMP CONTROL / STANDBY/ TYPE OF CONTROL)
ON
f Check the current flow rate.
Parameter
WP WATER FLOW RATE (INFO/ HEAT PUMP/ PROCESS DATA)
f Compare the value with the minimum flow rate (see chapter
"Specification/ Data table").
Minimum flow rate has been reached
No further measures required.
f Reset the parameters to their original values.
Parameter Setting
MINIMUM PUMP RATE (COMMISSIONING/ CHARGING
PUMP CONTROL / STANDBY/ TYPE OF CONTROL)
ON
MAXIMUM PUMP RATE (COMMISSIONING/ CHARGING
PUMP CONTROL / STANDBY/ TYPE OF CONTROL)
OFF
Minimum flow rate has not been reached
f Check the technical guide to the heating system.
12.3.3 Systems without a buffer cylinder
In systems without a buffer cylinder, the minimum flow rate of the
heat pump must be ensured via permanently open heating circuits
for the underoor heating system.
The design of the underfloor heating system determines the pos-
sible flow rate through the permanently open heating circuits.
If the flow rate of the permanently open heating circuits is less
than the minimum flow rate of the heat pump, check whether the
available external delivery head of the heating circulation pump
is sufficient.