INSTALLATION
Preparation
8 | WPL-A Premium www.stiebel-eltron.com
9.2 Safety clearances as required by the safety
concept
!
WARNING Injury
Refrigerant is heavier than air. In the case of leaks, es-
caping refrigerant can enter rooms beneath the instal-
lation site through open windows. If refrigerant escapes
from the appliance, it sinks and displaces the air. There
is risk of suffocation.
f Install the appliance at an adequate distance from
light wells.
f Ensure that the appliance is not installed in front of or above
supply air, extract air or other ventilation equipment.
In order to comply with the appliance's safety concept, safety
clearances to light wells must be observed.
Installation on foundation, light well at ground level
≥1000
≥1000
D0000091448
f Ensure that the minimum clearances to light wells are ob-
served.
Installation on foundation, light well above ground level
≥100≥100
≥150
D0000093454
f Ensure that the minimum clearances to light wells are ob-
served.
Installation on a mounting bracket
Note
The safety clearances to the light wells apply to the fol-
lowing mounting brackets:
- MK1 mounting bracket
- T-support SK1
- Wall mounting support WK 2
≥1000
≥1000
D0000091931
≥1000
≥1000
≥150
D0000093526
f Ensure that the minimum clearances to light wells are ob-
served.