SYMPTOMS RECTIFICATIONS
Home UPS mode, but no output Check the position of rotary switch at
the back panel.
Check if over temp. Shutdown
protection is displayed. Allow the unit
to cool down.
Check if low battery protection is
displayed. Allow the battery to
charge.
Check if overload/short circuit
protection is displayed. Reduce load
and switch OFF/ON front panel
switch. Check wiring for short
circuit.
Mains power is coming. Home UPS
shows MCB trip on its LCD
Panel.
Short circuit protection at the
time of installation.
Buzzer beeps continuously with
.
'Charging current status changed'
message is displayed.
Reduce load and switch ON mains
MCB at the rear panel and restart
Home UPS
If again the MCB trips, then Please
check the mains wiring for short
Circuit and call our customer care.
Input mains is connected to the output of
the Home UPS. Please check & correct
the Wiring Immediately
Battery Charger status is changed from
back panel. To activate restart Home UPS,
else change the position of switch to
previous mode.
Trouble shooting Trouble shooting
Trouble
Shooting
(12)
DSP Sine Wave Home UPSDSP Sine Wave Home UPS
Trouble shooting Trouble shooting
SYMPTOMS
Buzzer beeps with 'UPS Temp: High'
& message is displayed.
Fan is not Running
LCD displays 'Routine Reminder:
PI check battery water level &
restart Home UPS along with
Buzzer beeps
Check fan at the back panel. Shutdown
UPS & allow it to cool down.If
problem is repeated continuously,
Please call our customer care.
Check the fan status at display panel, if
fan status : OFF, then intelligent fan
control mode is active. ELSE if fan
status : ON, then call our customer
care.
This is a routine reminder that repeats
after every 3 months. Please check
battery water Level, do water topping
& restart Home UPS. To ignore reset
Home UPS.
RECTIFICATIONS
Trouble
Shooting
(13)