(d) Turn the AC circuit breaker to the
position "ON".
(e) Turn on the switch of the appliance.
ON
ON
OFF
The duplex 120V receptacle is protected by a GFCI (Ground Fault Circuit
Interrupter). GFCI shuts off the output current from the duplex 120V
receptacle when a ground fault occurs in the generator or the appliance.
Please note that other receptacles are not protected by GFCI.
[
CAUTION
]
GFCI RECEPTACLE
After starting the engine, check the GFCI for proper functioning by the following test
procedure.
Push blue TEST button, The red RESET button will pop out exposing the word
TRIP. Power is now off at the outlets protected by the GFCI, indicating that the
device is functioning properly.
If TRIP dose not appear when testing, do not use the generator. Call a qualified
electrician.
To restore power, push RESET button.
If the RESET button pops out during operation, stop the generator
immediately and call a qualified electrician for checking generator and
the appliances.
WARNING