DHL Regenerative Dryer w/SHDC-2300 touch screen controller User Manual US-EN
30
MODBUS ALARM MAP 6.2
MODBUS ALARM MAP
The TCP/IP modbus location is on 400001 as a 16 bit word.
The designated IP is 192.168.1.10 on port 502, but should broadcast to any IP.
PLC IP is 192.168.1.5
0= RIGHT TANK FAIL TO SHIFT
1= LEFT TANK FAIL TO SHIFT
2=RIGHT TANK FAILURE TO DEPRESS
3=LEFT TANK FAILURE TO DEPRESS
4=RIGHT TANK DEW POINT EXCEEDED
5=LEFT TANK DEW POINT EXCEEDED
6=FILTER NEEDS TO BE CHANGED
7=DEW POINT ALARM SET
15=NO ALARMS ACTIVE
(Figure 6.2) Modbus alarm map
(Figure 6.3) IO-List