DHL HEATLESS REGENERATIVE DRYER SECTION 6
36
Even if the DewPoint found is lower that the set SPC
value; the towers switch every 30 minutes. If the
applied load is close to the nominal load, the SHDC-
2100 device automatically moves to FIX mode (the
LED OFIX shows that this mode has been enabled,
and it remains on together with the LED ODPD), and
returns to DPD mode when the DewPoint values
drop again below the SPC value.
To better control the DPD cycle, the DewPoint value is calculated in the middle section of each
tower. Of course the measured value is higher than the DewPoint at the outlet of the dryer.
In case of defects and/or troubles with the PDP Meter, the SHDC-2100 device automatically
enters FIX mode.