SECTION 3 PRODUCT USER MANUAL
 133
The unit will not run or
cycles off and on.
 
 
 
 
 
Excessive compressed air 
inlet temperature.
Design conditions and correc-
tion factors are described in 
this manual.
Be sure that dryer is working 
in ambient temperatures 
below design conditions.
The dryer is designed for working 
into calculated design conditions. 
Should the conditions be 
exceeded, the dryer will be over-
flowed, dew point will go up and 
protecting devices may trip. 
Excessive ambient tem-
perature
Designed conditions and cor-
rection factors are described 
in  dryer . Be sure that dryer is 
working lower than design
conditions.
A high ambient temperature may 
cause the refrigerant system to 
operate at higher than normal 
pressures.  Results will be a
higher than normal evaporator 
temperature.
Important: there should be ade-
quate air circulation around the 
dryer, and proper ventilation in 
the equipment room should guar-
antee a low enough ambient tem-
perature.
Clogged condenser fins Clear fins of all obstructions. The clogged fins in the con-
denser will restrict the air pas-
sage and reduce the refrigeration 
capacity, causing high tempera-
ture in the evaporator.
Fins should be periodically 
checked and cleaned.
Shortage of refrigerant Fix the leak and add a charge 
of refrigerant.
Loss of refrigerant will cause 
improper functioning. 3-phase 
dryers are equipped with a tem-
perature switch which  maintains 
the amount of refrigerant to main-
tain proper cooling of the com-
pressor. 
A shortage of refrigerant may 
cause  suction line to become 
very hot, causing the temperature 
switch to trip. 
A qualified refrigeration specialist 
should perform the necessary 
repairs, or the factory should be 
contacted if the unit is in war-
ranty.
Err sign occurs on
digital temperature
control device
The dew point is too low or 
too high.
Check refrigerant gas and 
make sure that the working
conditions are within the cor-
rect range.
If there is not enough refrigerant-
gas or if the working temperature-
and inlet temperatures are very 
high, the dew point will increase.
Problem Possible Cause Repair Comments