SRC Service Manual
Revision 02
Aug 2007
12.5 Cleaning the Condensate Strainer
The internal strainer of the drain valve should be cleaned at
least every four to six months.
Unscrew the cap at the bottom side of the drain valve.
Remove the strainer.
Clean the strainer with compressed air.
Replace the strainer.
Tighten the cap firmly, but do not over-tighten.
12.6 Replacing the Coolant Pump
Be
indi
sure to recover the coolant – don’t dispose of it. Coolant tank capacities are
cated in Section 2.3. The total amount of coolant in the circuit is approximately 5 to
10% above tank capacity. Coolant is 42% glycol, 58% water. Proper tools may be
required to verify the correct mixture if coolant is being added.
Remove the coolant from the charge/discharge port on the bottom of the coolant tank.
Remove the old pump by disconnecting it from the system at the flanges.
Replace flange gaskets and install the new pump.
Recharge the coolant from the charging/discharging port.
Charge / Discharge Port Flanges