EasyManua.ls Logo

Sumitomo HF-520 Series - Note; Terminal Functions

Sumitomo HF-520 Series
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
Terminal Functions
Main Terminals
No. Terminal Name Function
R/L1
Main circuit power supply input
Connects line power to the drive.
Drives with single-phase 200 V input power use terminals R/ L1 and S/L2 only.
T/L3 must not be used.
S/L2
T/L3
U/T1
Drive output Connects to the motor.V/T2
W/T3
B1
Regenerative braking resistor Available for connecting a regenerative braking resistor.
B2
+1
DC reactor connection
These terminals are shorted at shipment.
Remove the shorting bar between +1 and +2 when connecting a DC reactor to this terminal.
+2
+1
DC power supply input For connecting a DC power supply.
(2 terminals) Ground
Grounding Terminal
200V Class 100Ω or less
400V Class 10Ω or less
Input Terminals
Type No. Terminal Name (Function) Function (Signal Level)
Multi-Function
Digital Inputs
S1
Multi-function input 1
(Closed: Forward run, Open: Stop)
Photocoupler
24 Vdc, 8 mA
Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24
Vdc (±10%) external power supply.
S2
Multi-function input 2
(Closed: Reverse run, Open: Stop)
S3 Multi-function input 3 (External fault (N.O.)
S4 Multi-function input 4 (Fault reset)
S5
Multi-function input 5
(Multi-step speed reference 1)
S6
Multi-function input 6
(Multi-step speed reference 2)
S7 Multi-function input 7 (Jog reference)
SC
Multi-function input common
(Control common)
Sequence common
Safe Disable
Input
HC Power supply for safe disable input +24 Vdc (max 10 mA allowed)
H1 Safe disable input
Open: Output disabled
Closed: Normal operation
Main
Frequency
Reference
Input
RP
Multi-function pulse train input
(frequency reference)
Response frequency: 0.5 to 32 kHz
(Duty Cycle: 30 to 70%)
(High level voltage: 3.5 to 13.2 Vdc)
(Low level voltage: 0.0 to 0.8 Vdc)
(input impedance: 3 kΩ)
+V Analog input power supply +10.5 Vdc (max allowable current 20 mA)
A1
Multi-function analog input 1
(frequency reference)
Input voltage 0 to +10 Vdc (20 kΩ) resolution 1/1000
A2
Multi-function analog input 2
(frequency reference)
Input voltage or input current (Selected by DIP switch S1) 0 to +10 Vdc (20 kΩ),
Resolution: 1/1000 4 to 20 mA (250 Ω) or 0 to 20 mA (250 Ω),
Resolution: 1/500
AC Frequency reference common 0 V
Output Terminals
Type No. Terminal Name (Function) Function (Signal Level) Default Setting
Multi-Function
Digital Output
MA N.O. (fault)
Digital output
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA (reference value)
MB N.C. output (fault)
MC Digital output common
Multi-Function
Photocoupler
Output
P1 Photocoupler output 1 (During run)
Photocoupler output 48 Vdc, 2 to 50 mA <2>P2 Photocoupler output 2 (Frequency agree)
PC Photocoupler output common
Monitor Output
MP Pulse train output (Output frequency) 32 kHz (max), DC5-12V (50% duty)
AM Analog monitor output 0 to 10 Vdc (2 mA or less) Resolution: 1/1000
AC Monitor common 0 V