EasyManua.ls Logo

Sunpak S34?TSR - Ventilation and Initial Start-Up; Initial Start-Up Procedure

Sunpak S34?TSR
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Sunpak® Infrared Heaters
9
Ventilation
1. It is required that areas above the heater be
properly vented to allow for necessary
combustion air and removal of combustion gases.
2. Heaters shall be provided with natural or
mechanical means to supply and exhaust at least
4 cfm per 1,000 BTU per hour of heater input.
Exhaust opening for removing the flue products
shall be above the level of the heaters.
3. Heater ventilation must comply with state and
local codes.
Fire Sprinklers
Fire Sprinklers must be located at an appropriate
distance from each heater to avoid accidental activation
of the sprinkler. Ethylene glycol or propylene glycol must
never be used in fire sprinkler systems where heaters are
present as these substances may become flammable
when heated. A fire sprinkler professional must be
consulted when heaters are installed where fire sprinklers
are present to insure that heaters and the fire sprinkler
system are properly integrated. Specific guidelines can be
found in NFPA 13 regarding design and specifications for
Fire Sprinkler Systems near heaters.
Initial Start-Up Procedure
1. Before turning on the manual gas valve to the heater
verify that the control system is working properly.
a. Make this is 7.5-6.0 VDC to the heater.
b. Press the ON button
c. There should be sparking at the pilot.
d. With the gas turned off the heater should turn
“OFF” or lockout in within 10 seconds.
e. Press the OFF Button to RESET Heater
2. Turn “ON” the manual gas valve
a. Press the ON button followed by the HI bottom.
b. Heater should be operated on HI for first 5
minutes to allow heater to warm up
c. Press the LOW button, the burner should burn
cooler.
d. If heater locks out, press the OFF Button to
RESET Heater and repeat start up sequence.
e. If the heater locks out several times there may
still be air in the gas line.
NOTE: Some white smoke may appear
during or just after the initial start-up of the
heater. White smoke will dissipate with
proceeding use.
Regular Service and Maintenance
Overtime,particularlyduringlongperiodsofnon
use,theheatercanaccumulatedirtanddebrisin
andaroundthepilotandtheburner.Routine
maintenanceshouldbeperformedatleastoncea
yearbyaqualifiedserviceagencytoinsurethe
heaterisoperatingproperly.Morefrequentservice
may
berequiredforheaterslocatednear
waterfronts.
Battery Life
Boththewallcontrolandhandheldremotesuse
batteriesavailableatthelocalhardwarestore.
Pleasekeepinmindthefollowing:
Weak batteries can reduce the range of the
transmitter.
Batteries should be removed if heaters are not
to be used for a long period of time.
Dispose of used batteries properly
Two #2032 Button Batteries power the wall control transmitter
They are available at your local hardware store
.
Loss of Programming
Although each heater comes pre-programmed for two
devices, this programming can be lost if the following
occurs:
ElectricalPowerSurge
Heaterisdisconnectedalongperiodoftime.
Morethanthreedeviceshavebeenprogrammed
fortheheater.